Greenheck Vgn - Greenheck Vektor Installation, Operation And Maintenance Manual

Laboratory exhaust with variable geometry nozzle (vgn) technology electrical controls information
Table of Contents

Advertisement

Electrical Controls Information for Customer-Supplied Variable Frequency Drive

GREENHECK VGN

DIAGNOSTIC
INPUT B1
XX.X
INPUT ID1
XXXXX
OUTPUT NO1
XXXXX
OUTPUT Y2
XX.X
OUTPUT Y4
XX.X
22
VGN Technology
The following value ranges are specific to the Diagnostic menu screen. The menu
will tell the controls electrician who is troubleshooting the system what the status
is of each Input or Output of the controller.
Input B1 Value of B1 analog input of the controller (pressure transducer).
0 VDC to 10 VDC
Input ID1 Status of the ID1 digital input of the controller (fan status).
Open or Closed
Output NO1 Status of the NO1 digital output of the controller (alarm contact).
Open or Closed
Output Y2 Value of the Y2 analog output of the controller (nozzle actuator).
2 VDC to 10 VDC
Output Y4 Value of the Y4 analog output of the controller (BMS CFM scale).
0 VDC to 10 VDC
All of these points can be verified with a volt meter between the terminal point
specified and system common using either voltage or continuity settings on the
meter.
The values in this menu are not user-editable and are locked by the controller program.
®