TREND HT/S Installation Instructions
TREND HT/S Installation Instructions

TREND HT/S Installation Instructions

Space humidity and temperature sensor

Advertisement

Quick Links

Space Humidity and Temperature Sensor
Important: Retain these instructions
These instructions shall be used by trained service personnel only
If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.
conTenTS
1

Unpacking .....................................................................1

2
Installation .....................................................................1
1
UnpackIng
2
InSTallaTIon

Dimensions

1
86 mm (3.39")
Mounting Requirements
2
HT/S Space Humidity and Temperature Sensor Installation Instructions TG200990 Issue 2, 19-Mar-2013
3
4
HT/S Installation Instructions (TG200990)
Replacing an HT/S with HT/S V2: Re-wire the humidity
connection as described below, set the controller's input
connected to sensor's humidity output to voltage, and change
the scaling used by the sensor type module to use the correct
scaling see step (9).
26 mm (1.02")

Installation Instructions

Maintenance ..................................................................4
Disposal .........................................................................4
It is recommended that the installation should comply
with the local electrical safety installation practices (e.g.
HSE Memorandum of Guidance on Electricity at Work
Regulations 1989, USA National Electric Code).
> 50 cm (20")
1.5 m (5 ft)
HT/S
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HT/S and is the answer not in the manual?

Questions and answers

Summary of Contents for TREND HT/S

  • Page 1: Installation Instructions

    (9). 86 mm (3.39”) 26 mm (1.02”) Mounting Requirements > 50 cm (20”) 1.5 m (5 ft) HT/S Space Humidity and Temperature Sensor Installation Instructions TG200990 Issue 2, 19-Mar-2013...
  • Page 2 Remove Backplate Mount Backplate either Back Box (BeSa) 35 mm (1.38”) 35 mm (1.38”) or Wall Box or Wall 35 mm (1.38”) Remove cutouts Route cables (as required) HT/S Space Humidity and Temperature Sensor Installation Instructions TG200990 Issue 2, 19-Mar-2013...
  • Page 3 (V) linked for thermistor (T) HT/S/2% In order to maintain the HT/S/2% temperature sensor accuracy, the temperature sensor should only be used if the humidity sensor is also used. earth (ground) screen at IQ end humidity...
  • Page 4 Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited. Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Table of Contents