nanoeX check mode
To enable nanoeX check mode, during nanoeX operation ON:
o
During nanoeX check mode, H67 is judged when disconnection detected. Timer LED blinks.
o
nanoeX Abnormal Detection
Disconnection Abnormality
o
Abnormal detection condition
Start from 1 sec after nanoeX power ON, 6 secs has passed and in this 6 secs period, abnormal
signal is detected continuously for 5.9 secs.
Action after abnormal detection condition fulfilled
Disconnection counters +1, nanoeX power OFF for 5 minutes and then restart. However, according
to action mode and disconnection counter, below will be implemented:
During nanoeX Check Mode: Disconnection abnormality will judged when disconnection counter
o
≥ 1. Abnormal code: H67 will memorized in EEPROM, Timer LED blinking and nanoeX LED Off.
Other Than Above: Disconnection abnormality will judged when disconnection counter ≥ 3.
o
Abnormal code: H67 will memorized in EEPROM and nanoeX LED OFF, Timer LED not blinking.
Disconnection counters clear condition >
Disconnection counter will be cleared when operation stop. (Not nanoeX Check Mode)
nanoeX Discharge Abnormality
o
Abnormal detection condition
After 30 minutes nanoeX power ON, abnormal signal is being detected continuously for 5s.
Action after abnormal detection condition fulfilled
Abnormal discharge counter +1, nanoeX power OFF for 30 minutes and then restart. When abnormal
discharge counter ≥ 12, abnormal code: H67 in analyze area (Area where abnormal code not
displayed) will be memorized.
Abnormal discharge counters clear condition
Discharge counter will be cleared when operation become normal for 50 mins above or when
operations stop.
Normal display mode
Press
SW (t ≥ 0 secs)
When
SW pressed continuously for t ≥ 5 secs to enter service zone
and press
SW's to choose function 57
Transmit
"NANOEX CHECK" code