12.1.4.4
Insulating the refrigerant piping
Attach the pipe after checking for gas leakage,
described above.
1
Cut the insulated portion of the on-site piping,
matching it up with the connecting portion.
2
Secure the slit on the auxiliary pipe side with
the butt joint on the connection pipe using the
tape, making sure there are no gaps.
3
Wrap the slit and the butt joint with the
included insulation sheet, making sure there
are no gaps.
12.1.4.5
Checking for gas leakage
Check for leakage of gas after air purging.
See the in the installation manual for the outdoor.
CAUTION
1) Insulate the joint of the pipes securely.
Incomplete insulation may lead to water leakage.
2) Push the pipe inside so it does not apply undue force on the front grille.
12.1.5
Connecting the Indoor/Outdoor
Connection Cable
Guide connection cable pass through refrigerant
piping port and lead the connection cable into the
control box.
Check the color of the wires on the terminal board
and secure them with screws.
Secure the connection cable with cord holder.
Guide and push the connection cable inside so
that it does not apply undue force on the front
grille.
Fix the connection cable into cable holder.
WARNING
This equipment must be properly earthed.
When the wall is hollow, please be sure to use the sleeve for
tube ass'y to prevent dangers caused by mice biting the
connection cable.
Connection cable between indoor unit and
outdoor unit should be approved polychloroprene
sheathed 4 x 1.5 mm
type 60245 IEC 57 (H05RN-F) or heavier cord.
Allowable connection cable length of each indoor
unit shall be 30 m or less.
Ensure that the terminal numbers on the
o
indoor unit are connected to the same
terminal numbers on the outdoor unit by the
right coloured wires as shown in the diagram.
CAUTION
2
flexible cord, designation
) 1
Auxiliary pipe
Slit
Earth lead wire should be longer than the
o
other lead wires as shown in the diagram for
electrical safety purpose in case the cord slips
out from the anchorage.
Secure the cable onto the control board with the
holder (clamper).
Terminals on the indoor unit
Colour of wires
Terminals on the outdoor unit
Ensure the colour of wires of outdoor unit and the
terminal Nos. are the same to the indoor's
respectively.
Earth wire shall be Yellow/Green (Y/G) in colour
and longer than other AC wires for safety reason.
Cable holder
Connection cable
Refrigerant piping port
29
2)
) 3
Auxiliary pipe
Auxiliary pipe
Slit
Insulation sheet
Tape
Connection
pipe
Check for leakage here.
• Apply soapy water and
check carefully for leaking
gas.
• Wipe soapy water off after
the check is complete.
1
2 3
1
2 3
Terminal Board
Cord
Connection cable
holder
3
Earth Wire
longer than
others AC wires
for safety reason