ClimateMaster ATA11H01 Installation Instructions page 2

Microelectronic thermostat

Advertisement

ATA11H01
MICROELECTRONIC THERMOSTAT
Mode Number
(Press i key
to change)
Select
Not used
25 thru 32
Minimum off
33
time for the
compressor
Heating setpoint
34
range stop
Cooling setpoint
35
range stop
Not used
36
Temperature
37
display
adjustment
69-1312—1 G.H. Rev. 5-99 Printed in Taiwan R.O.C.
69-1312
Table 2. Thermostat installer setup options (continued).
Factory-Setting
Display
Description
00
No minimum off time for
the compressor
80
Heating setpoint can be
set no higher than 80°F
60
Cooling setpoint can be
set no lower than 60°F
00
No difference in
displayed temperature
and actual room
temperature
T8501D
R
C
Y
R
C
Y1
DXM TERMINALS
T8501D
R
C
Y
R
C
Y
CXM TERMINALS
FACTORY INSTALLED JUMPERS.
1
Display
01, 02,
03, 04
or 05
40 thru
90
45 thru
c
99
-03 thru
03
1
O
G
W
O/W2
G
AL1
1
O
G
W
O
G
AL1
2
Other Choices
(Press
or
key to change)
Description
Minimum number of minutes
(0 thru 5) the compressor will be
off between calls for the
compressor
Number can be set anywhere
between 40 and 90 in 1°F
increments
Number can be set anywhere
between 45 and 99 in 1°F
increments
01—Display adjusts to 1°F higher
than actual room temperature
02—Display adjusts to 2°F higher
than actual room temperature
03—Display adjusts to 3°F higher
than actual room temperature
-01—Display adjusts to 1°F lower
than actual room temperature
-02—Display adjusts to 2°F lower
than actual room temperature
-03—Display adjusts to 3°F lower
than actual room temperature
X1
X1
M14304
www.honeywell.com/yourhome