Eltek BC2000 Operation Manuals page 38

Compact, integreted, hj, and j front wire dc power systems
Table of Contents

Advertisement

Parameter
Activate
Manual BDT
Activates the battery discharge test if
enabled under the "Battery Mgt" menu.
(Executable)
Manual Boost
Activates battery boost if enabled under the
"Battery Mgt" menu.
(Executable)
Enables or disables the relay test function,
Test Mode
which permits controller output relays to be
activated
Activates a single controller output relay.
Relay (A-F)
Test Mode must be enabled.
Lamptest
Temporarily illuminates all LEDs (controller,
display, rectifiers, etc)
(Executable)
Battery Mgt
Enables or disables the battery discharge
BDT State
test feature. If enabled, "Manual BDT"
appears under the "Activate" menu.
The length of time that the battery discharge
BDT Duration
test is scheduled to run
An alarm is triggered if the battery terminal
BDT Alarm V
voltage falls below this value during the
battery discharge test
If the battery terminal voltage falls below this
value during the battery discharge test, the
BDT Abort V
battery discharge test is aborted and an
alarm is triggered. This value should be at
least 2V below BDT Alarm V
The time in minutes the controller waits after
BDT Alarm
the test has dropped below the BDT Alarm V
Delay
to trigger the alarm
BDT Auto
Enables the automatic BDT Start Mode
Mode
Enables or disables the battery boost /
Boost State
equalize function
Boost
Duration of time the equalize / boost is active
Duration
The voltage to which the equalize / boost
Boost Voltage
charge increases
Boost Stop
Stops the boost mode if the current value has
Current
gone below this set point
Generator*
State
Enables or disables the generator feature
Select the type of generator in use (either air-
Type
cooled or "other")
38
Display Operation Manual BC2000 and JC2000 Controller ~ Doc. No. 2055882, Issue 5.1, June 2014
Description
Default
Value Range
Setting
NA
NA
NA
NA
Disabled /
Disabled
Enabled
Inactive /
Inactive
Active
NA
NA
Disabled /
Disabled
Enabled
00:30:00
Max 17:59:59
(HH:MM:SS)
44 – 53 V
52 V
(Min: BDT
abort +1 to -1)
43 – 52 V
(Min: LVD
Disconnect V +
43 V
1V,
Max: BDT
Alarm V. 1V)
15 mins
0 – 30 mins
Disabled /
Disabled
Enabled
Disabled /
Disabled
Enabled
12:00:00
Max
255:59:59
(HH:MM:SS)
56.5 V
55 – 57 V
0A
0 – 255 A
Disabled /
Disabled
Enabled
Air Cooled /
Other
Other

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Eltek BC2000

This manual is also suitable for:

Jc2000

Table of Contents