QUICK INSTALLATION GUIDE

Remote Management Card
RMCARD202
I ntelligent Remote Management Card allows a UPS
system to be managed, monitored, and configured

INSTALLATION GUIDE

Step 1. Hardware Installation
1. Turn off the UPS before
removing the expansion port
cover on the UPS.
2. Remove the two retaining
screws of the expansion port
cover then remove the cover.
3. Install the CyberPower Remote
Management Card into the
expansion port.
4. Re-install and tighten the
retaining screws.
5. Connect the Ethernet cable
to the LAN port of the
CyberPower Remote
Management Card.
6. Turn on the UPS.
Definitions for LED Indicators
Link LED color
TX/RX LED color
Step 2. Configure the IP address for the CyberPower
Method 1: Using the Power Device Network Utility Tool
1. Install the Power Device Network Utility Tool from the included CD. It
is located on the CD in the \tools\nework folder. Double click the
"Power Device Network Utility" installation file, "Setup.msi" to begin
the installation.
K09-0000064-02
2. After installation is completed, run the "Power Device Network Utility"
program. (Under "All Programs", select "CyberPower Power Device
Network Utility").
3. The main dialog of the Power Device Network Utility Tool program is
shown in Figure 1. The tool will display all Remote Management
Cards present on the network. The "Refresh" button is used to search
the entire local network again.
4. Select the Remote Management Card you are setting up. Click on the
Tools menu and select "Device Setup" or double click the Remote
Management Card you want to configure.
5. You can modify the IP Address,
Subnet Mask, and Gateway
address for the Device MAC
Address listed in the Device
Network Settings window, as
shown in figure 2. The default IP
Address is 192.168.20.177 and
the default Subnet Mask is
255.255.255.0.
6. Modify the IP, subnet mask or
gateway address. Enter the new
addresses into the
corresponding fields.
LINK Indicator
Link
The Remote Management Card is not
connected to the Network or the Remote
Off
Management Card power is off
The Remote Management Card is connected
On(Yellow)
to the Network
 
Off
The Remote Management Card power is OFF
On(Green)
The Remote Management Card power is ON
- Receiving/transmitting data packet
Flash
- Reset finished
Remote Management Card.
Figure 1. The main window of the "Power Device Network Utility" program.
Ethernet connector
RX/TX Indicator
RX/TX
RMCARD202
Condition
Figure 2. The Device Network setting window.

Advertisement

loading

Summary of Contents for CyberPower RMCARD202

  • Page 1: Quick Installation Guide

    - Receiving/transmitting data packet Flash - Reset finished Step 2. Configure the IP address for the CyberPower Remote Management Card. Method 1: Using the Power Device Network Utility Tool 1. Install the Power Device Network Utility Tool from the included CD. It is located on the CD in the \tools\nework folder.
  • Page 2: Trouble Shooting

    If yellow led is off : CyberPower North America ►Check if the network connection is valid. CyberPower Systems (USA), Inc. 2. Check if the operated PC is on the same Phone: (952)-403-9500 Toll-free: (877)297-6937 physical network as Remote Management 4241 12th Avenue E.