E-Clipse Bypass Configurations for ACH550 Drives
Group 14
Code
Name
1411
R4 ON DLY
1412
R4 OFF DLY
1413
RO5 SELECT
1414
R5 ON DLY
1415
R5 OFF DLY
Group 16
Code
Name
1601
START/STOP
1602
RUN
ENABLE
1603
START EN 1
1604
START EN 2
1605
START EN 3
1606
START EN 4
1607
RESET SRC
Resolution
Range
0.1 sec
0-3600.0s
0.1 sec
0-3600.0s
1
See RO 1 Select.
0.1 sec
0-3600.0s
0.1 sec
0-3600.0s
Resolution
Range
1
0 = NOT SEL
1 = DI1
2 = COMM
1
0 = NOT SEL
1 = DI2
2 = COMM
1
0 = NOT SEL
1 = DI3
2 = COMM
1
0 = NOT SEL
1 = DI4
2 = COMM
1
0 = NOT SEL
1 = DI5
2 = COMM
1
0 = NOT SEL
1 = DI2
2 = COMM
1
0 = NOT SEL
1 = DI4
2 = COMM
Default
Description
0s
Delay from active state to active
output.
0s
Delay from inactive state to
inactive output.
BYPASS
AUTO
(13)
0s
Delay from active state to active
output.
0s
Delay from inactive state to
inactive output.
Default
Description
DI 1
Selects source for system start
(1)
command.
NOT SEL
Selects source for run enable
(0)
command.
DI 3
Selects source for start enable 1
(1)
command.
NOT SEL
Selects source for start enable 2
(0)
command.
NOT SEL
Selects source for start enable 3
(0)
command.
NOT SEL
Selects source for start enable 4
(0)
command.
NOT SEL
Selects source for fault reset
(0)
command (rising edge).
Parameter Descriptions