Electrical Component Specifications - Mitsubishi Electric PEFY-P20VMR-E-L Technical & Service Manual

Table of Contents

Advertisement

[ III SPECIFICATIONS ]

3-2. Electrical component specifications

Model
Symbol
Component
Transformer
Room temperature
TH21
thermistor
Liquid pipe
TH22
thermistor
Gas pipe thermistor
TH23
Fuse
(Control board)
Fan motor
(with Inner-
thermostat)
Inner-thermostat
(Fan motor)
Fan motor capacitor
Linear expansion
valve
Power supply
terminal block
Transmission
TB5 TB15
terminal block
PEFY-P20VMR-E-L/R
T
Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
Resistance 0°C/15kΩ, 10°C/9.6kΩ, 20°C/6.3kΩ, 25°C/5.4kΩ, 30°C/4.3kΩ, 40°C/3.0kΩ
F1
MF
C1
LEV
TB2
PEFY-P25VMR-E-L/R
(Primary) 50/60Hz 220-240V (Secondry) (23.5V 0.9A)
250V 6.3A
4-pole, Output 18W
OFF 135°C±5°C ON 86°C±15°C
1.5µF × 440V
12VDC Stepping motor drive port diameter ø3.2
(0~1800 pulses <on R410-compatible outdoor units>,
0~2000 pulses <on other types of outdoor units>)
(L, N,
) 330V 30A
(1, 2), (M1, M2, S) 300V 10A
- 5 -
PEFY-P32VMR-E-L/R
4-pole, Output 23W

Hide quick links: