Carrier 19XR Start-Up, Operation And Maintenance Instructions Manual page 72

Hermetic centrifugal liquid chillers 50/60 hz with pic ii controls and hfc-134a
Hide thumbs Also See for 19XR:
Table of Contents

Advertisement

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
C. IN RECYCLE SHUTDOWN
PRIMARY MESSAGE
RECYCLE RESTART PENDING
RECYCLE RESTART PENDING
RECYCLE RESTART PENDING
RECYCLE RESTART PENDING
D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary.
PRIMARY
STATE
MESSAGE
100
PRESTART
STARTS LIMIT
ALERT
EXCEEDED
101
PRESTART
HIGH BEARING
ALERT
TEMPERATURE
102
PRESTART
HIGH MOTOR
ALERT
TEMPERATURE
103
PRESTART
HIGH DISCHARGE
ALERT
TEMP
104
PRESTART
LOW REFRIGERANT
ALERT
TEMP
105
PRESTART
LOW OIL
ALERT
TEMPERATURE
106
PRESTART
HIGH CONDENSER
ALERT
PRESSURE
107
PRESTART
LOW LINE
ALERT
VOLTAGE
108
PRESTART
HIGH LINE
ALERT
VOLTAGE
109
PRESTART
GUIDE VANE
ALERT
CALIBRATION
*[LIMIT] is shown on the CVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE]
is the actual pressure, temperature, voltage, etc., at which the control tripped.
E. START-UP IN PROGRESS
PRIMARY MESSAGE
STARTUP IN PROGRESS
STARTUP IN PROGRESS
STARTUP IN PROGRESS
AUTORESTART IN PROGRESS OCCUPIED MODE
AUTORESTART IN PROGRESS REMOTE CONTACT CLOSED
AUTORESTART IN PROGRESS START COMMAND IN EFFECT Chiller is starting after power failure. Chiller START/STOP on MAINSTAT
Table 8 — CVC Primary and Secondary Messages and
SECONDARY MESSAGE
OCCUPIED MODE
REMOTE CONTACT CLOSED
START COMMAND IN EFFECT
ICE BUILD MODE
SECONDARY
ALARM MESSAGE
MESSAGE
PRIMARY CAUSE
100->Excessive compressor
starts (8 in 12 hours)
101->Comp Thrust Bearing
Temp [VALUE] exceeded
limit of [LIMIT]*.
102->Comp Motor Winding
Temp [VALUE] exceeded
limit of [LIMIT]*.
103->Comp Discharge
Temp [VALUE] exceeded
limit of [LIMIT]*.
104->Evaporator Refrig
Temp [VALUE] exceeded
limit of [LIMIT]*.
105->Oil Sump Temp
[VALUE] exceeded limit of
[LIMIT]*.
106->Condenser Pressure
[VALUE] exceeded limit of
[LIMIT]*.
107->Average Line Voltage
[VALUE] exceeded limit of
[LIMIT]*.
108->Average Line Voltage
[VALUE] exceeded limit of
[LIMIT]*.
109->Actual Guide Vane
Pos Calibration Required
Before Start-Up
SECONDARY MESSAGE
OCCUPIED MODE
REMOTE CONTACT CLOSED
START COMMAND IN EFFECT Chiller is starting. Chiller START/STOP in MAINSTAT manually
PROBABLE CAUSE/REMEDY
Unit in recycle mode, chilled water temperature is not sufficiently above
set point to start.
Unit in recycle mode, chilled water temperature is not sufficiently above
set point to start.
Chiller START/STOP on MAINSTAT manually forced to start, chilled
water temperature is not sufficiently above set point to start.
Chiller in ICE BUILD mode. Chilled fluid temperature is satisfied for ICE
BUILD conditions.
ADDITIONAL CAUSE/REMEDY
Depress the RESET softkey if additional start is
required. Reassess start-up requirements.
Check oil heater for proper operation.
Check for low oil level, partially closed coil supply
valves, clogged oil filters, etc.
Check the sensor wiring and accuracy.
Check configurable range in SETUP1 screen.
Check motor sensors for wiring and accuracy.
Check motor cooling line for proper operation, or
restrictions.
Check for excessive starts within a short time span.
Check configurable range in SETUP1 screen.
Allow discharge sensor to cool.
Check for sensor wiring and accuracy.
Check for excessive starts.
Check configurable range in SETUP1 screen.
Check transducer wiring and accuracy.
Check for low chilled fluid supply temperatures.
Check refrigerant charge.
Check oil heater contactor/relay and power.
Check oil level and oil pump operation.
Check transducer wiring and accuracy.
Check for high condenser water temperatures.
Check voltage supply. Check voltage transformers.
Consult power utility if voltage is low.
Check voltage supply.
Check power transformers.
Consult power utility if voltage is high.
Calibrate guide vane actuator in Control Test.
CAUSE/REMEDY
Chiller is starting. Time schedule is occupied.
Chiller is starting. Remote contacts are enabled and closed.
forced to start.
Chiller is starting after power failure. Time schedule is occupied.
Chiller is starting after power failure. Remote contacts are enabled
and closed.
manually forced to start.