USING THIS MANUAL USING THIS MANUAL A. INSTALLATION SEQUENCE DANGER Follow the installation instructions provided in this manual Indicates a condition or hazard which will cause in the order shown. The order of these instructions has severe personal injury, death or major property been set in order to provide the installer with a logical damage.
PRODUCT SAFETY & INFORMATION PRODUCT SAFETY & INFORMATION DANGER WARNING HOT WATER CAN SCALD! Protection must be taken against excessive temperature and pressure! • Water temperatures over 125ºF can cause severe burns instantly or death from scalding. • Installation of a Temperature & Pressure (T&P) relief valve is required.
“open ® ® 1. Single wall heat exchanger in the Peerless Partner system”. Exposing the outer tank of the water heater water heater complies with National Standard...
1. Water heater should be installed to allow adequate 4. Refer to boiler manual for boiler clearances. clearance for servicing. 5. See Figure 1.1 for recommended service clearances. 2. Zero clearance is permissible to any side of the Peerless ® Partner ® water heater, but information labels may be hidden.
6" of the floor. Refer to local codes. water heater. • plugged, reduced or restricted. • subject to freezing. Every Peerless ® Partner ® water heater must be protected with a T&P relief valve.
0.1 severe personal injury, death, or substantial property mg/liter-day for boiler and water heater protection. damage. NOTICE THERMOSTATIC MIXING VALVE The Peerless ® Partner ® IDWH must be installed on a closed type hydronic system. Failure to provide such 1.
Page 14
INSTALLATION - PIPING DRAWINGS Figure 3.6: Peerless ® Partner ® Boiler Piping with Zone Valves Figure 3.7: Peerless ® Partner ® Boiler Piping with Zone Circulators...
Page 15
(Refer to the PureFire ® Installation, Maintenance, and Operations Manual for alternate piping configurations). Figure 3.9: Peerless ® Partner ® Boiler Piping for Peerless ® ® Condensing Boilers Note: Contact PB Heat for optional heat exchanger kit for "Double Wall" applications.
Page 16
• A maximum of 3 water heaters may be piped in series. ® ® • Utilize the lead (hot water outlet) Peerless Partner tank thermostat to control system temperature. • Install automatic mixing valve at either the hot water outlet of the water heater system or at each hot water fixture.
INSTALLATION - WIRING 4. INSTALLATION – WIRING B. CIRCULATORS WARNING Priority relay must be sized for total amp draw of all Electrical shock hazard can cause severe personal circulators. injury, death or substantial property damage. Disconnect power before installing and/or servicing. C.
Page 22
INSTALLATION – WIRING DRAWINGS Figure 5.7: Circulator Zoning Without Domestic Priority, Series MI Figure 5.8: Circulator Zoning Without Domestic Priority, Series WBV/WV, WV-DV, EC, SC...
Page 23
INSTALLATION – WIRING DRAWINGS Note: Maximum of 4 total circulator zone when wiring 1 zone for priority. Figure 5.9: Priority Zoning Circulator Wiring...
WATER HEATER START-UP 6. WATER HEATER START-UP 6. If antifreeze is used in boiler water, check A. FILLING THE INNER (DOMESTIC WATER) concentration. Boiler water (including additives) must TANK be practically non-toxic, having toxicity rating or class of 1, as listed in Clinical Toxicology of Commercial CAUTION Products.
20ºF higher. or service technician. WARNING At no time should boiler limit control be set above 210°F. This can cause severe personal injury, death or substantial property damage if ignored. Figure 6.2: Peerless ® Partner ® Knob...
WATER HEATER MAINTENANCE 7. WATER HEATER MAINTENANCE A. MAINTENANCE SCHEDULE B. FILLING WATER HEATER Annual service by qualified service technician should include See “Filling the Inner (Domestic Water) Tank and “Filling the the following: Outer (Boiler Water) Tank” on in Section 6.A and 6.B. 1.
WATER HEATER MAINTENANCE D. DRAINING INNER (DOMESTIC WATER) E. DRAINING OUTER (BOILER WATER) TANK TANK 1. Disconnect snap set wiring connection at water. (See Domestic Piping Fig. 3.1) 2. Close boiler water isolation valves between boiler and 1. Disconnect snap set wiring connection at water heater. water heater.
TROUBLESHOOTING 8. TROUBLESHOOTING Table 8.1: Troubleshooting Problem Cause Solution Refer to boiler installation instructions Boiler does not operate Check main service switch Check fused disconnect Check power supply Circulator does not operate Check circulator switching relay No hot water at faucet. Improper tank thermostats setting or calibration Turn tank thermostat to higher setting Zone valve does not open (if used)
1st Hour Flow Continuous Flow Circulator Model Number Capacity MBH Gallon/10 Minute Gallon/Hour Gallon/Hour Minimum GPM PT-30 PT-40 PT-50 PT-60 PT-80 PT-120 Conditions: 50°F Domestic Cold Water Inlet Temperature 140°F Domestic Hot Water Outlet Temperature 200°F Boiler Water Supply Temperature Table 11.2...
Page 33
PERFORMANCE RATINGS Table 11.5 First Hour Ratings for Reduced Boiler Output (Gallons) Boiler PT-30 PT-40 PT-50 PT-60 PT-80 PT-120 Output 140°F 115°F 140°F 115°F 140°F 115°F 140°F 115°F 140°F 115°F 140°F 115°F (MBH) Note: shaded values are recommended only for PureFire ®...