Preventive Maintenance; Water Quality Table; Condensate Trap - Trane Axiom GEHB 006 Installation, Operation And Maintenance Manual

Horizontal/vertical water-source comfort system
Table of Contents

Advertisement

Preventive Maintenance

Maintenance on the unit is simplified
with the following preventive
suggestions:
Filter maintenance must be
performed to assure proper
operation of the equipment. Filters
should be inspected at least every
three months, and replaced when it
is evident they are dirty. Filter sizing
includes:
Table 6.
Size
Size
Filter Size
60 HZ
50 HZ
GEH
006-015
006-012
14 5/8" x 20 1/4"
(371 x 514)
018-030
015-024
16 3/8" x 23 5/8"
(416 x 600)
036-042
030-036
18 5/8" x 25 3/8"
(473 x 645)
048-060
042-060
20 5/8" x 29 3/4"
(524 x 755)
072-120
072-090
20 x 20 (3)
(508 x 508)
150-180
120-150
25 x 25 (3)
(635 x 635)
GEV
006-015
006-012
15 7/8" x 19 7/8"
(403 x 504)
018-030,
015-024
17 7/8" x 24 7/8"
040
(454 x 632)
036-042
030-036
19 7/8" x 24 7/8"
(504 x 632)
048-060
042-060
27 7/8" x 29 7/8"
(708 x 759)
GEV 072-
090
20 x 20 (4)
120
(508 x 508)
150-300
120-240
19 5/8" x 24 5/8" (6)
(498 x 625)'
WSHP-SVX01E-EN
Maintenance
WARNING
Hazardous Voltage!
Disconnect all electric power,
including remote disconnects before
servicing. Follow proper lockout/
tagout procedures to ensure the
power can not be inadvertently
energized. Failure to disconnect
power before servicing could result
in death or serious injury.
Check the contactors and relays
within the control panel at least once
a year. It is good practice to check the
tightness of the various wiring
connections within the control panel.
A strainer (60 mesh or greater) must
be used on an open loop system to
keep debris from entering the unit
heat exchanger and to ensure a clean
system.
For units on well water, it is
important to check the cleanliness of
the water-to-refrigerant heat
exchanger. Should it become
contaminated with dirt and scaling
as a result of bad water, the heat
exchanger will have to be back
flushed and cleaned with a chemical
that will remove the scale. This
service should be performed by an
experienced service person.
WARNING
Hazardous Chemicals!
Coil cleaning agents can be either
acidic or highly alkaline. Handle
chemical carefully. Proper handling
should include goggles or face
shield, chemical resistant gloves,
boots, apron or suit as required. For
personal safety, refer to the cleaning
agent manufacturers Materials
Safety Data Sheet and follow all
recommended safe handling
practices. Failure to follow all safety
instructions could result in death or
serious injury.
It should be noted that the water
quality should be checked
periodically. See
Table
7.
Table 7.

Water Quality Table

Scaling
Calcium and
Less than 350 ppm
magnesium (total
hardness)
Corrosion
pH
7-9.5
Hydrogen Sulfide
Less than 1 ppm
Sulfates
Less than 25 ppm
Chlorides
Less than 125 ppm
Carbon Dioxide
Less than 75 ppm
Total dissolved solids
Less than 1000
(TDS)
ppm
Biological Growth
Iron Bacteria
Low
Erosion
Suspended Solids
Low

Condensate Trap

For units incorporating a negative
trap design, ensure that the
condensate system is primed with
water at all times. Allowing a
negative, pressure condensate
system to run dry could cause a
break in the condensate seal
allowing the fan to draw water from
the condensate line to spray
moisture into the mechanical
system. By maintaining a primed
condensate trap, a seal will be
created and will help prevent these
complications.