Deluxe Board Diagnostics; Low Voltage Connection (6 To 25 Ton); Controls Using 24 Vac - Trane Axiom GEHB 006 Installation, Operation And Maintenance Manual

Horizontal/vertical water-source comfort system
Table of Contents

Advertisement

Controls Using 24 VAC

There are two factory thermostat
options for the dual circuited (6
through 25 ton) equipment. Low
voltage connection diagrams for
deluxe 24 volt control packages for
these thermostats mounted on 6
through 25 ton equipment sizes are
shown in
Figure
63.
For controls using DC analog input/
outputs, see appropriate installation,
operation and diagnostic manuals for
connection. WSHP-IOP-2 (ZN510) and
WSHP-PRB002-EN (ZN524).
Deluxe Controls with
-all Heat Pump Units w/ Reheat
-all Cooling Only Units
using X13511090010 (T8511)
1TB2
1
24 VAC (R)
2
FAN (G)
COMPRESSOR 1 (Y1)
3
4
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
5
6
24 VAC COMMON (C) & WATER ISOLATION VA
COMPRESSOR DISABLE
7
8
COMPRESSOR DISABLE
9
ALARM
ALARM
10
11
ELECTRIC HEAT
ELECTRIC HEAT
12
13
HUMIDISTAT
WATER ISOLATION VALVE
14
15
3RD STAGE HEAT (W3)
NOT USED
16
Deluxe Controls with
-all Heat Pump Units without Reheat
using X13511090010 (T8511)
1TB2
1
24 VAC (R)
FAN (G)
2
3
COMPRESSOR 1 (Y1) & WATER ISOLATION VA
4
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
5
6
24 VAC COMMON (C) & WATER ISOLATION VA
COMPRESSOR DISABLE
7
8
COMPRESSOR DISABLE
ALARM
9
10
ALARM
ELECTRIC HEAT
11
12
ELECTRIC HEAT
13
HUMIDISTAT
NOT USED
14
15
3RD STAGE HEAT (W3)
NOT USED
16
Figure 63.

Low voltage connection (6 to 25 ton)

Deluxe Board Diagnostics

Three light emitting diodes (LEDs)
are provided for indicating the
operating mode of the Deluxe
Controller. The LEDs are intended to
aid in troubleshooting and for unit
maintenance. The LEDs are labeled
on the circuit board with numbers as
referenced in
Table
34.
WSHP-SVX01E-EN
Installation
Deluxe Controls with
-all Heat Pump Units w/ Reheat
-all Cooling Only Units
using X13511091010/X13511092010 (T7300)
1TB2
1
24 VAC (R)
2
FAN (G)
COMPRESSOR 1 (Y1)
3
4
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
5
6
24 VAC COMMON (X) & WATER ISOLATION VA
COMPRESSOR DISABLE
7
8
COMPRESSOR DISABLE
9
ALARM
ALARM
10
11
ELECTRIC HEAT
ELECTRIC HEAT
12
13
HUMIDISTAT
WATER ISOLATION VALVE
14
15
3RD STAGE HEAT (W1)
NOT USED
16
Deluxe Controls with
-all Heat Pump Units without Reheat
using X13511091010/X13511092010 (T7300)
1TB2
1
24 VAC (R)
FAN (G)
2
3
COMPRESSOR 1 (Y1) & WATER ISOLATION VA
4
COMPRESSOR 2 (Y2)
REVERSING VALVE (0) & HUMIDISTAT
5
6
24 VAC COMMON (X) & WATER ISOLATION VA
COMPRESSOR DISABLE
7
8
COMPRESSOR DISABLE
ALARM
9
10
ALARM
ELECTRIC HEAT
11
12
ELECTRIC HEAT
13
HUMIDISTAT
NOT USED
14
15
3RD STAGE HEAT (W1)
NOT USED
16
Table 34.
Deluxe controller diagnostic
LEDs
Color: Green
Color: Red
LED1
LED2
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
FLASH
ON
ON
FLASH
ON
FLASH
ON
ON
ON
ON
ON
FLASH
ON
ON
Controller
LED3
Mode
OFF
Control OFF
OFF
Normal/Compressor OFF
FLASH
Anti-short cycle
ON
Normal/Compressor ON
OFF
Brownout Condition
ON
Soft Lockout (low pressure)
FLASH
Soft Lockout (high pressure)
ON
Manual Lockout (low pressure)
FLASH
Manual Lockout (high pressure)
OFF
Manual Lockout (condensate overflow)
OFF
Compressor Disable
57