Return-Air Duct Panel; Opening Size And Part Number; Take Off Side Panel; Dual Filtration (Geh 1/2 To 5 Ton) - Trane Axiom GEHB 006 Installation, Operation And Maintenance Manual

Horizontal/vertical water-source comfort system
Table of Contents

Advertisement

Dual Filtration (GEH 1/2
to 5 ton)
Note: The dual-filtration design is
typically used in a free-return
application.
The horizontal, GEH model, allows
the installer flexibility in design
applications such as a dual filtration
option. With the dual filtration
design, the unit will contain a lower
static which translates into a
decrease in filter maintenance. For
installation of a dual filtration
accessory for the GEH model, verify
that an extra set of return-air filter
racks and filter have been ordered
from the factory. This accessory will
be shipped separate from the unit,
and should be located in a separate
box than the unit.
1.
Remove the return-air side panel
from the GEH unit. This panel is
held in place by six Torx® head
screws.
Figure 48.

Take off side panel

2.
Install the top/bottom filter rack
at the new opening. The 1"/2"
(25.4/50.8 mm) adjustable filter
rack is held in place with four
Torx® head screws that once
held the panel.
Figure 49.
Install top/bottom filter
rack
WSHP-SVX01E-EN
Installation
3.
Install the 1"/2" (25.4/50.8 mm)
filter.
Figure 50.
Install filter

Return-Air Duct Panel

Note: The ducted panel design is
typically used in combination
with a field installed ceiling
filter rack design.
The return-air arrangement may be
easily converted from a free return-
air system, to a ducted return-air
system with the addition of a return-
air side panel on the GEH unit. By
replacing the filter racks with the
return-air panel, a complete seal
from the ductwork to the unit is
possible. The 1 1/2" (38 mm) duct
flange facilitates ease of field hook-
up to the mechanical system.
1.
Install the return-air duct panel to
the return-air opening with the
six Torx® head screws provided
for the filter rack assembly.
Table 31.

Opening size and part number

Unit Size
Unit Size
60 HZ
50 HZ
A
006-015
006-012
17 1/2" (445) 13" (330)
018-030
015-024
20 1/2" (521) 15" (381)
036-042
030-036
22 1/2" (572) 17" (432)
048-060
042-060
26 1/2" (673) 19" (483)
Unit Top
A
3 3/4
"
Figure 51.
Install return air duct
panel
Duct Collar
B
Part Number
4474 1133 0100
4474 1134 0100
4474 1135 0100
4474 1136 0100
B
DUCT PANEL
with 1 1/2"-FLANGE
51