OFFSET FOR T1 TEMPERATURE READINGS CALIBRATION
Use the offset feature in stand alone configuration, when there is no wall panel.
The technician will measure the required temperature in the room (according to
which he would like to make the offset for T1).
In order to update the offset, the following steps must be followed:
- Press and hold the emergency [On/Off] button for more than 15 seconds.
The system will enter to a "Calibration" mode. In this mode the beeper will beep
each 5 seconds, and both blue and red LED's will flash together and beep sound
will continue until out of the calibration mode.
- Once the system is in "calibration mode" the technician will adjust the set point
in the remote control as the measured actual ambient, and send to the IR re-
ceiver.
- This temperature will be read, and the difference form the actual T1 measure-
ment will be calculated into an offset of T1 = "ReturnAirSensorCalibration", and
accordingly the parameter will be updated.
- If no information is sent from the remote control, after 2 minutes from the start
of "calibration mode", the system will automatically return to normal operation
mode.
- After the technician has sent the "calibration temperature" from the remote the
system will automatically return to normal operation mode.
SWING
AUTOMATIC VERSION
The unit (model RC only) automatically placed the blades according to the mode
of operation.
In cooling mode the blades remain in parallel position to exploit the benefits of
the Coanda effect, while in heating mode are positioned with an opening of 35°
in order to exploit the effect of anti-stratification.
Nel caso in cui l'impostazione automatica (contrassegnata nel telecomando col
simbolo
) sia stata modificata in impostazione manuale (simbolo
nare alla modalità standard definita dal produttore procedere come segue:
- Press the [Select] button 5 times (the icon
- Press the [-] button to select auto swing (
- Press the [On/Send] button to send the information to the unit.
In this way the blades will set the standard position established by the manu-
facturer.
MANUAL VERSION
If there is the need to change the inclination of the blades manually, to change
the air flow differently from the standard position set in automatic way, proceed
as follows:
- Press the [Select] button 5 times (the icon
- Press the [+] button to select manual swing (
- Press the [On/Send] button to send the information to the unit.
In this way the blades will reverse their position respect to automatic version.
Vers. 2015-3
), per tor-
will flash).
).
Pic. 27
will flash).
).
Pic. 28
18
BATTERIES REPLACEMENT
When the batteries are low, the display of the remote control will dim.
If the batteries will not be replaced the display will turn off completely.
Batteries replacement:
- Pull the batteries cover down to reveal the batteries.
- Remove the old batteries.
- Wait for 10 minutes before installing the new batteries.
- Install two new AAA batteries – Pay attention to the polarity.
- Return the batteries cover to place.
IMPORTANT
THE I.R. REMOTE CONTROL WILL NOT OPERATE UNLESS AT LEAST
10 MINUTES PASS BETWEEN REMOVING THE OLD BATTERIES AND IN-
STALLING THE NEW ONES.