Rheem GE Series Use And Care Manual page 8

Electric residential water heaters single and double element models, residential 20–120 gallon
Table of Contents

Advertisement

Installing the water heater.
Ground screw
Junction
Conduit
box
connector
cover
Wire connections
Water heater junction box.
CAUTION: The presence
of water in the piping and
water heater does not
provide sufficient
conduction for a ground.
Non-metallic piping,
dielectric unions, flexible
connectors etc. can cause
the water heater to be
electrically isolated.
NOTICE: This guide recommends minimum branch circuit sizing and wire size based on National Electric Code.
Refer to wiring diagrams in this manual for field wiring connections.
8
Electrical Connections
A separate branch circuit with copper
conductors, overcurrent protective device
and suitable disconnecting means must
be provided by a qualified electrician.
All wiring must conform to local codes
or latest edition of National Electrical
Code ANSI/NFPA 70.
The water heater is completely wired to
the junction box inside jacket at the top
front of the water heater. An opening for
1/2" or 3/4" electrical fitting is provided
for field wiring connections.
The voltage requirements and wattage
load for the water heater are specified
on the rating plate on the front of the
water heater.
Branch Circuit Sizing and Wire Size Guide
Total Water
Recommended Over Current Protection
Heater Wattage
(fuse or circuit breaker amperage rating)
208V
3,000
20
4,000
25
4,500
30
5,000
30
5,500
35
6,000
40
8,000
50
9,000
10,000
11,000
12,000
The branch circuit wiring should
include either:
Metallic conduit or metallic
sheathed cable approved for use as
a grounding conductor and
installed with fittings approved for
the purpose.
Non-metallic sheathed cable,
metallic conduit or metallic
sheathed cable not approved for
use as a ground conductor shall
include a separate conductor for
grounding. It should be attached to
the ground terminals of the water
heater and the electrical
distribution box.
240V
277V
480V
20
15
15
25
20
15
25
25
15
30
25
15
30
25
15
35
30
20
45
40
25
50
45
25
50
30
50
30
35
Copper Wire Size AWG Based
on N.E.C. Table 310-16 (75°C)
208V
240V
277V
480V
12
12
14
14
10
10
12
14
10
10
10
14
10
10
10
14
8
10
10
14
8
8
10
12
8
8
8
10
8
8
10
8
10
8
10
8