Baldor BC140 Installation And Operation Manual page 44

Scr dc motor control
Hide thumbs Also See for BC140:
Table of Contents

Advertisement

Table 10-1 Troubleshooting Guide for Controls without Optional Forward-Brake-Reverse
Symptom
Erratic motor performance.
Motor continues to run with
Main Speed Potentiometer
set fully counterclockwise.
Motor runs in wrong
direction.
44
Switch Installed (Continued)
Possible Cause
Overload condition.
Incorrect Plug-In Horsepower
Resistor
.
®
CL and/or IR Trimpots may be set
incorrectly.
Defective speed control module.
Voltage Select Switch set to wrong
position.
Defective motor, worn brushes, etc.
MIN speed trimpot set higher than
0% of base speed.
IR Comp trimpot set too high.
Motor armature leads are reversed.
Suggested Corrective Action
Remove overload.
Install the correct Plug-In
Horsepower Resistor
. See Table
®
4-3.
Readjust the CL and/or IR Trimpots,
as described in Section 7.
Replace speed control.
Recheck line voltage and the
correct setting of the Voltage Select
Switch, as described in Section 6.
Repair or replace motor.
Readjust the MIN Trimpot, as
described in Section 7.
Readjust the IR Trimpot, as
described in Section 7.
Reconnect motor armature leads.