CLIMATIC™ 60 – AIRCOOLED CHILLERS
ALARM 081, 083, 085, 089, 090, 141, 142, 143, 144, 145, 146, 148, 149, 241, 242, 243, 244,
 Description
The temperature probe or pressure sensor measured by the CLIMATIC™ 60 or other expansion boards is
incorrect. The device may be disconnected or in short circuit for 5s.
• Alarm 081: The inlet water evaporator temperature probe value is incorrect,
• Alarm 083: The outside air temperature probe value is incorrect,
• Alarm 085: The outlet water evaporator temperature probe value is incorrect,
• Alarm 089: The inside electrical box air temperature probe value is incorrect,
• Alarm 090: The inlet freecooling water temperature probe value is incorrect,
• Alarm 141: The high pressure sensor value on the circuit 1 is incorrect,
• Alarm 142: The low pressure sensor value on the circuit 1 is incorrect,
• Alarm 143: The liquid temperature probe value on the circuit 1 is incorrect,
• Alarm 144: The suction temperature probe value on the circuit 1 is incorrect,
• Alarm 145: The discharge temperature probe value on the circuit 1 – compressor 1 is incorrect,
• Alarm 146: The discharge temperature probe value on the circuit 1 – compressor 2 is incorrect,
• Alarm 148: The inlet water condenser temperature probe value on the circuit 1 is incorrect,
• Alarm 149: The outlet water condenser temperature probe value on the circuit 1 is incorrect,
• Alarm 241: The high pressure sensor value on the circuit 2 is incorrect,
• Alarm 242: The low pressure sensor value on the circuit 2 is incorrect,
• Alarm 243: The liquid temperature probe value on the circuit 2 is incorrect,
• Alarm 244: The suction temperature probe value on the circuit 2 is incorrect,
• Alarm 245: The discharge temperature probe value on the circuit 2 – compressor 1 is incorrect,
• Alarm 246: The discharge temperature probe value on the circuit 2 – compressor 2 is incorrect,
• Alarm 248: The inlet water condenser temperature probe value on the circuit 2 is incorrect,
• Alarm 249: The outlet water condenser temperature probe value on the circuit 2 is incorrect.
 Action
• Alarm 081: Immediate shut down of the complete unit. The alarm is signalling,
• Alarm 083: Immediate shut down of the complete unit. The alarm is signalling,
• Alarm 085: Immediate shut down of the complete unit. The alarm is signalling,
• Alarm 089: Doesn't stop the unit. The alarm is signalling,
• Alarm 090: Doesn't stop the unit. The alarm is signalling.
• Alarm 141: Immediate shut down of the circuit 1. The alarm is signalling,
• Alarm 142: Immediate shut down of the circuit 1. The alarm is signalling,
• Alarm 143: Immediate shut down of the circuit 1. The alarm is signalling,
• Alarm 144: Immediate shut down of the circuit 1. The alarm is signalling,
• Alarm 145: Immediate shut down of the circuit 1. The alarm is signalling,
• Alarm 146: Immediate shut down of the circuit 1. The alarm is signalling,
• Alarm 148: Immediate shut down of the circuit 1 and the circuit 2, only if there is one condenser for the both
circuits,
• Alarm 149: Immediate shut down of the circuit 1 and the circuit 2, only if there is one condenser for the both
circuits,
MUL41E-0610/06-2011
245, 246, 248, 249:
PROBE & SENSOR, FAULTY
Page 85