9.15 Adjusting Maximum Heating Power
Maximum boiler heating power can be reduced to suit
requirements of heating system it serves.
Table showing parameter P13 values according to desired
maximum power model is shown for each single boiler.
To access and edit P13 values, proceed as described in
Parameter Settings.
Boiler Model - PARAMETER P13 (%)/ Heating Output
Btu/h
20,400
23,800
27,200
30,700
34,100
40,900
47,700
54,500
61,400
68,200
75,100
81,900
88,700
95,500
102,300
109,200
112,600
9 - START UP PROCEDURE
KW
MAH-125 MAC-150
6.0
0
0
7.0
4
3
8.0
7
6
9.0
11
9
10.0
15
12
12.0
22
18
14.0
30
24
16.0
37
29
18.0
44
35
20.0
52
41
22.0
59
47
24.0
67
53
26.0
74
59
28.0
80
65
30.0
88
71
32.0
96
75
33.0
100
80
Btu/h
kW
27,400
8.0
31,300
9.2
35,800
10.5
41,300
12.1
46,500
13.6
55,900
16.4
65,700
19.3
74,500
21.8
83,200
24.4
92,300
27.0
101,900
29.9
110,000
32.2
118,000
34.8
127,000
37.2
136,900
40.1
145,300
42.6
151,700
44.4
47
MAH-165 MAC-205
0
0
4
3
7
6
11
9
15
12
22
18
30
24
37
29
44
35
52
41
59
47
67
53
74
59
80
65
88
71
96
75
100
80
240011941 REV B, [03/31/2018]