Specifications - PrimeVOLT V-3000N-V Installation & Operation Manual

Single phase on-grid pv inverter
Table of Contents

Advertisement

13. Specifications

Model
Input (DC)
Recommended
Max. Power
2
MPPT Range
(full load)
Working Range
Max. DC Voltage
Max. DC Current
No. of MPP Trackers
I
PV
SC
Max. backfeed
current to array
Output (AC)
Nom. Power
Max. Power
Nominal Voltage
Voltage Range
Nominal Frequency
Power Factor
Maximum Current
Max. O/P Over-
Current Protection
Efficiency
Max. Efficiency
Euro- Eta
General
Temp. Range
Temp. Full Power
1
5000W for VDE-AR-N 4105
2
MPPT range: According to EN50524, it is range under nominal AC power
3
4600W for VDE-AR-N 4105
4
4600W for VDE-AR-N 4105
5
20A for VDE-AR-N 4105
6
Voltage Range: 184~264.5 for VDE-AR-N 4105
Unit
PV-3000N-V
W
3300
V
315~500
V
100~580
V
580
A
10
1
A
15
mA
1.6
W
3000
W
3000
V
V
Hz
A
14.3
A
20
%
97.2
%
96.4
°C
°C
55
PV-5000W-V
1
5500
290~500
100~580
580
10 x 2
2
15 x 2
1.6
3
5000
4
5000
220/230/240
6
184~264.5
50/60
-0.8 ~ +0.8
5
23.8
40
97.2
96.1
-20 ~ 55
-20 ~ 45
PV-5000W-HV
1
5500
180 ~ 980
550 ~ 800
980
10
1
14
1.0
3
5000
4
5000
5
23.8
45
97.7
97.4
-25 ~ 60

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pv-5000w-vPv-5000w-hv

Table of Contents