Fieldpiece ASX14 Operator's Manual

Fieldpiece ASX14 Operator's Manual

Superheat and subcooling head for r22 and r410a with pipe clamp thermocouple

Advertisement

Quick Links

Superheat and
Subcooling Head for
R22 and R410A
with pipe clamp
thermocouple
Model: ASX14
STABLE
Air
ON
Conditioner
Superheat
LO BATT
and Subcooling
SH
R22
ENGLISH
R410A
SC
METRIC
SH or SC
Temp
Pressure
Set
T/C
AUTO-
ATM
Cal
OFF
ASX14
OPERATOR'S MANUAL

SPECIFICATIONS

Operating environment: 32ºF to 122ºF; 0ºC to
50ºC at <75%RH
Allow ~5 min. for ASX14 to come to ambient temp.
Storage environment: -4ºF to 140ºF; -20ºC to
60ºC at <80%RH with battery removed.
Battery life: 25 hours typical. No measurable
current draw when in "off" position.
Low battery indication: Red LED lights
Battery: 9V
Auto off: Approx. 15 minutes
Overloads: The ASX14 outputs 3.4V when tem-
perature or pressure is outside of their working
range (overloaded). For ranges below
3400mVDC, the normal overload symbol will be
displayed on the meter ("OL"). For ranges
above 3400mVDC, reading displayed will be
approximately 3.4VDC.
Stated Accuracy: at 73°F ± 9°F (23°C ±5°C) ,
<90% R.H.
Temperature
Range (temperature): -40ºF to 400ºF;
-40ºC to 204ºC
Resolutions: 0.1º
Sensor type: k-type thermocouple
Pipe clamp thermocouple accuracy: ±4ºF
(±2°C) or ±0.75%, whichever is greater, -30ºF to
200ºF (-34°C to 93°C)
System accuracy: ±1ºF;±0.06ºC @ 73ºF ± 5ºF
Description
The model ASX14 superheat and subcooling
accessory head measures refrigerant pressure and
temperature simultaneously. It then calculates and
displays superheat or subcooling. It has a 1/4"
industry standard fitting for actual pressure. A pipe
clamp thermocouple is included for temperature.
Select R22 or R410A. Select superheat or subcool-
ing.Select english or metric units.
Use it your way
STABLE
Air
ON
Conditioner
Superheat
LO BATT
and Subcooling
R22
SH
ENGLISH
STABLE
R410A
SC
METRIC
Air
STABLE
ON
Air
ON
Conditioner
Conditioner
Superheat
Superheat
and Subcooling
LO BATT
SH or SC
and Subcooling
LO BATT
Temp
Pressure
R22
SH
ENGLISH
R22
SH
ENGLISH
R410A
SC
METRIC
R410A
SC
METRIC
Set
T/C
ATM
Cal
AUTO-
SH or SC
OFF
SH or SC
Temp
Temp
Pressure
Pressure
ASX14
Set
T/C
Set
T/C
ATM
Cal
AUTO-
ATM
Cal
AUTO-
OFF
OFF
ASX14
ASX14
OFF
2000
EHDL1 AHDL1 w/ Meter
DL3
after ice water calibration (see Field calibration).
Pressure and vacuum
Working range (pressure):
0 to 500 psi; 0 to 4000 kPa
Max displayed pressure: 800psi (5500 kPa)
Working range (vacuum):
29"Hg vac. to 0; 74cmHg vac. to 0
Vacuum will show up as negative value on meter.
Resolutions: 0.1psi or kPa, 0.1"Hg or cmHg vac.
Accuracy:
0 to 200 psig, ±1 psi, 0 to 1378 kPa ±6.9 kPa;
200 to 500 psig, 0.3% ±1 psi, 1378 to 3447 kPa
0.3% ±6.9kPa
Sensor breakdown pressure: 800psi (5500 kPa)
Superheat
Range (temperature): 0ºF to 80ºF; 0ºC to 27ºC
Resolutions: 0.1º
System Accuracy: ±1ºF @ 73ºF ± 5ºF (±0.06ºC
@ 23°C ±3°C) after calibration (see Field cali-
bration).
Subcooling
Range (temperature): 0ºF to 80ºF; 0ºC to 27ºC
Resolutions: 0.1º
System Accuracy: ±1ºF @ 73ºF ± 5ºF (±0.06ºC
@ 23°C ±3°C) after calibration (see Field cali-
bration).
How to use
1. Connect to COM and Volts jack. Slide ASX14
superheat head onto Fieldpiece "stick" meter,
data logger, electronic handle or connect to
most other meters using Fieldpiece ADLS2
deluxe test leads or AHDL1 handle.
2. Set meter to mVDC range.
3. Calibrate if needed (see Field calibration)
4. Hand tighten 1/4" flare to suction line or liquid
line as close to the evaporator or condenser as
possible using an EPA approved service hose
(not included).
5. Select superheat or subcooling, refrigerant (R22
or R410A) and units (English or metric).
6. Connect the pipe clamp to the suction (super-
STABLE
Air
ON
Conditioner
Superheat
LO BATT
and Subcooling
heat) or liquid (subcooling) line at least six inch-
R22
SH
ENGLISH
R410A
SC
METRIC
es from the condenser and slide it under the
SH or SC
Temp
Pressure
insulation for best accuracy isolating the pipe
Set
T/C
ATM
Cal
AUTO-
OFF
clamp from the ambient air (pg. 2).
ASX14
7. Select parameter to display (superheat, sub-
cooling, pressure, or temperature).
8. You must wait until the system you are testing
has stabilized. The STABLE LED lights when
the reading is stable.
9. Disable Auto-off to data log any of the above
parameters with the DL3 data logger.
10. Once you have the superheat or subcooling
reading follow the manufacturer of the air condi-
HS30
tioner's specifications to properly charge or
diagnose the system.
Warranty
The ASX14, Superheat and Subcooling accesso-
ry head is warranted against manufacturer's defects
for one year. This warranty does not apply to
defects resulting from abuse, neglect, accident,
unauthorized repair, alteration, or unreasonable use
of the instrument. Any implied warranty arising out
of the sale of Fieldpiece's products including but not
limited to implied warranties of merchantability, and
fitness for purpose, are limited to the above.
Fieldpiece shall not be liable for incidental or con-
sequential damages.
Service
Return any defective ASX14 to Fieldpiece for
warranty service along with proof of purchase.
Contact Fieldpiece for out of warranty repair
charges.

Field calibration

Temperature: To calibrate the system (ASX14,
pipe clamp thermocouple, meter), adjust the cali-
bration pot underneath the rubber covering while
measuring a known temperature. Ice water is 32°F
(0°C) and is readily available.
1. Stabilize (by repeated stirring) a large cup of ice
water.
2. Select temperature on ASX14, plug in the pipe
clamp thermocouple and then immerse entire
clamp into the ice water (keep stirring).
3. Adjust the calibration pot to read 32.0 (0.0 if
using °C) on the DMM for optimum accuracy at
room temp.
Pressure: The pressure/vacuum reading prior to
connecting to an A/C system should always be
zero. If you see that you're getting pressure read-
ings of something other than zero without your serv-
ice hose attached, you need to set atmospheric
pressure before connecting the ASX14 to the sys-
tem. To set atmospheric pressure, press the button
underneath the rubber covering entitled "Set ATM".
You usually have to set atmospheric pressure each
time you dramatically change elevations. For exam-
ple, if you "Set ATM" in Denver and take a pressure
reading of an A/C system in Los Angeles, the pres-
sure reading in Los Angeles will be lower than it
actually is.
.