Fieldpiece ARH5 Operator's Manual

Fieldpiece ARH5 Operator's Manual

In-duct psychrometer head

Advertisement

Quick Links

Fieldpiece

Quick Start

1. Connect ARH5 to Fieldpiece meter.
In-Duct
2. Select mVDC range on meter.
3. Remove vinyl slip cover from the
Psychrometer
probe tip.
Head
4. Select desired switch position on
ARH5 for temperature, wet bulb,
dew point, or %RH.
OPERATOR'S
5. Read your measurement directly on
MANUAL
the display of the Fieldpiece meter.

Certifications

Model ARH5
80
In-Duct
ON
Psychrometer
Head
LO BATT
ON
°F
1%RH/mVDC
1°F/mVDC
1°C/mVDC
OFF
°C
TEMP
WET BULB
DEW POINT
%RH
AUTO OFF
ARH5
Do not retract the sensor probe by pulling on the cord.
Doing so may sever the cord from the sensors.
01
02
Fieldpiece
Quick Start
1. Connect ARH5 to Fieldpiece meter.
In-Duct
2. Select mVDC range on meter.
Psychrometer
3. Remove vinyl slip cover from the
probe tip.
Head
4. Select desired switch position on
ARH5 for temperature, wet bulb,
dew point, or %RH.
OPERATOR'S
5. Read your measurement directly on
MANUAL
the display of the Fieldpiece meter.
Certifications
Model ARH5
80
In-Duct
ON
Psychrometer
Head
LO BATT
ON
°F
1%RH/mVDC
1°F/mVDC
1°C/mVDC
OFF
°C
TEMP
WET BULB
DEW POINT
%RH
AUTO OFF
ARH5
Do not retract the sensor probe by pulling on the cord.
Doing so may sever the cord from the sensors.
01
02

Description

With your purchase of the ARH5 you
now have the ability to take supply/
return temperature, %RH, wet bulb
and dew point measurements from
inside the duct or plenum.
Use the telescopic probe to take
measurements in hard to reach places.
Yo u r A R H 5 m e a s u r e s b o t h
relative humidity and ambient
air temperature. It also calculates
dew point and wet bulb temperatures
automatically.
The ARH5 snaps directly onto
Fieldpiece HS series DMMs, Fieldpiece
C-Tick (N22675)
Datalogger or HVAC Guide® System
Analyzer. For other meters, use
CE
Fieldpiece ADLS2 test leads or the
AHDL1 handle adapter.
RoHS compliant
Use your ARH5 in combination with
the HVAC Guide and easily perform
Target Evaporator Exit Temperature
WARNING
tests and get more reliable and
c o nve n i e n t Ta r g e t S u p e r h e a t
calculations.
03
Description
With your purchase of the ARH5 you
now have the ability to take supply/
return temperature, %RH, wet bulb
and dew point measurements from
inside the duct or plenum.
Use the telescopic probe to take
measurements in hard to reach places.
Yo u r A R H 5 m e a s u r e s b o t h
relative humidity and ambient
air temperature. It also calculates
dew point and wet bulb temperatures
automatically.
The ARH5 snaps directly onto
Fieldpiece HS series DMMs, Fieldpiece
C-Tick (N22675)
Datalogger or HVAC Guide® System
Analyzer. For other meters, use
CE
Fieldpiece ADLS2 test leads or the
AHDL1 handle adapter.
RoHS compliant
Use your ARH5 in combination with
the HVAC Guide and easily perform
Target Evaporator Exit Temperature
WARNING
tests and get more reliable and
c o nve n i e n t Ta r g e t S u p e r h e a t
calculations.
03

Specifications

Go wireless with your ARH5 by
using Fieldpiece wireless transmitters
Telescoping Probe Length: Up to 38 inches (97cm)
(ET2W/EH4W) to send measurements
Probe Tip Diameter: 0.35 inch (9mm)
over-the-air to Fieldpiece wireless
Storage temperature: -4°F to 140°F (-20°C to 60°C), 0
receivers (HG3, LT17AW, EH4W )
to 80% RH (with battery removed)
anywhere on the jobsite.
Temperature Coefficient: 0.1 x (specified accuracy)/°C
(<18°C or >28°C)
Use the RCONE1 for hands-free
Power: Single standard 9-volt battery, NEDA 1604, JIS
in-duct measurements.
006P, IEC 6F22
Auto Power Off: Approx. 15 minutes
Battery life: 150 hours typical (alkaline)
Low Battery Indication: Red LO BATT LED will light to
indicate low battery.
Output Impedance: 500Ω approx.
Dimensions: 144mm(H) x 67mm(W) x 32mm(D)
Weight: Approx. 240g, including battery
Temperature:
Sensor type: Precision thermistor
Operating environment: -4°F to 140°F (-20°C to 60°C)
Range: -4°F to 140°F (-20°C to 60°C)
Resolution: 0.1°F / 0.1°C
Accuracy: ±(1°F) 32°F to 113°F
ARH5 w/ ET2W
Output: 1mV to 1°F/°C
transmitting wirelessly to HG3
Figure 1
04
05
Specifications
Go wireless with your ARH5 by
using Fieldpiece wireless transmitters
Telescoping Probe Length: Up to 38 inches (97cm)
(ET2W/EH4W) to send measurements
Probe Tip Diameter: 0.35 inch (9mm)
over-the-air to Fieldpiece wireless
Storage temperature: -4°F to 140°F (-20°C to 60°C), 0
receivers (HG3, LT17AW, EH4W )
to 80% RH (with battery removed)
anywhere on the jobsite.
Temperature Coefficient: 0.1 x (specified accuracy)/°C
(<18°C or >28°C)
Use the RCONE1 for hands-free
Power: Single standard 9-volt battery, NEDA 1604, JIS
in-duct measurements.
006P, IEC 6F22
Auto Power Off: Approx. 15 minutes
Battery life: 150 hours typical (alkaline)
Low Battery Indication: Red LO BATT LED will light to
indicate low battery.
Output Impedance: 500Ω approx.
Dimensions: 144mm(H) x 67mm(W) x 32mm(D)
Weight: Approx. 240g, including battery
Temperature:
Sensor type: Precision thermistor
Operating environment: -4°F to 140°F (-20°C to 60°C)
Range: -4°F to 140°F (-20°C to 60°C)
Resolution: 0.1°F / 0.1°C
Accuracy: ±(1°F) 32°F to 113°F
ARH5 w/ ET2W
Output: 1mV to 1°F/°C
transmitting wirelessly to HG3
Figure 1
04
05
Relative Humidity:
Sensor Type: Capacitance polymer film
Operating environment: 32°F to 131°F (0°C to 55°C)
Range: 0% to 100%RH
Accuracy: ±(2.5%) 10% to 90%RH
±(5%) <10%RH and >90%RH
Note: Above accuracies stated at 73.4°F (23°C).
Output: 1mV to %RH
Sensor Response Time: 60 seconds typical for 90% of
total range.
Sensor Hystersis: ±1%RH typical (Excursion of 10% to
90% to 10%RH)
In-Duct
ON
In-Duct
ON
Psychrometer
Psychrometer
Head
Head
LO BATT
LO BATT
ON
°F
ON
°F
1%RH/mVDC
1%RH/mVDC
1°F/mVDC
1°C/mVDC
1°C/mVDC
1°F/mVDC
OFF
°C
OFF
°C
TEMP
TEMP
WET BULB
WET BULB
DEW POINT
DEW POINT
%RH
%RH
AUTO OFF
AUTO OFF
±(2°F) -4°F to 32°F, 113°F to 140°F
ARH5
ARH5
MAX 30VDC
24VAC
CONNECT ONLY TO
ACCESSORY HEAD!
±(0.5°C) 0°C to 45°C
ET2W
AC
±(1°C) -20°C to 0°C, 45°C to 60°C
DC
SEND
ON
Wireless
SYNC
Transmitter
RECEIVE
LO BATT
06
Relative Humidity:
Sensor Type: Capacitance polymer film
Operating environment: 32°F to 131°F (0°C to 55°C)
Range: 0% to 100%RH
Accuracy: ±(2.5%) 10% to 90%RH
±(5%) <10%RH and >90%RH
Note: Above accuracies stated at 73.4°F (23°C).
Output: 1mV to %RH
Sensor Response Time: 60 seconds typical for 90% of
total range.
Sensor Hystersis: ±1%RH typical (Excursion of 10% to
90% to 10%RH)
In-Duct
In-Duct
Psychrometer
ON
Psychrometer
ON
Head
LO BATT
Head
LO BATT
ON
°F
ON
°F
1%RH/mVDC
1%RH/mVDC
1°F/mVDC
1°F/mVDC
1°C/mVDC
1°C/mVDC
OFF
°C
OFF
°C
TEMP
TEMP
WET BULB
WET BULB
DEW POINT
DEW POINT
%RH
%RH
AUTO OFF
AUTO OFF
ARH5
±(2°F) -4°F to 32°F, 113°F to 140°F
ARH5
MAX 30VDC
24VAC
CONNECT ONLY TO
ACCESSORY HEAD!
±(0.5°C) 0°C to 45°C
ET2W
AC
DC
±(1°C) -20°C to 0°C, 45°C to 60°C
SEND
ON
SYNC
Wireless
Transmitter
RECEIVE
LO BATT
06
In-Duct
ON
In-Duct
Psychrometer
Psychrometer
ON
Head
Head
LO BATT
LO BATT
ON
°F
ON
°F
1%RH/mVDC
1%RH/mVDC
1°C/mVDC
1°F/mVDC
1°F/mVDC
OFF
°C
1°C/mVDC
OFF
°C
TEMP
WET BULB
TEMP
DEW POINT
WET BULB
%RH
DEW POINT
%RH
AUTO OFF
AUTO OFF
ARH5
ARH5
AUTO-OFF
WIRELESS
MAX/MIN
ENABLED
SYNC
HOLD
50500
600
600
500
50
5000m
5000m
500m
500m
RECV
500µ
500µ
50m
50m
200m
200m
750
500
2
K
200
20
500
1400
20
M
2
K
200
K
200
OFF
15 SEC FOR
500
m
V
RANGE
CAT.III
MAX
FUSED
600V
200
FUSED
m
A
MAX
30V
MAX
2
00
2 000
2000
In-Duct
Psychrometer
ON
In-Duct
ON
Head
Psychrometer
LO BATT
Head
LO BATT
ON
°F
°F
1%RH/mVDC
1%RH/mVDC
ON
1°F/mVDC
1°F/mVDC
1°C/mVDC
1°C/mVDC
OFF
°C
OFF
°C
TEMP
TEMP
WET BULB
WET BULB
DEW POINT
DEW POINT
%RH
%RH
AUTO OFF
AUTO OFF
ARH5
ARH5
AUTO-OFF
WIRELESS
MAX/MIN
ENABLED
SYNC
HOLD
600
600
50500
500
50
5000m
500m
5000m
500m
500µ
RECV
50m
50m
500µ
200m
200m
500
K
2
750
200
500
20
20
M
2
K
1400
200
K
200
OFF
15 SEC FOR
500
m
V
RANGE
CAT.III
MAX
FUSED
600V
FUSED
200
m
A
MAX
MAX
30V
2
2000
2 000
00

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ARH5 and is the answer not in the manual?