Download Print this page

Coleman P4HUE30N13006 Technical Manual page 2

Gas-fired furnaces, commercial belt- drive mid-efficiency multi-position, upflow & horizontal 130 mbh output 78 afue

Advertisement

036-21166 -001 REV A (0201)
FIGURE 1 : DIMENSIONS
Input
Model
MBH
P4HUE30N13006
160
*. AFUE numbers are determined in accordance with DOE test procedures.
†. Wire size and overcurrent protection must comply with the National electric code (ANSI / NFPA-70-latest edition)
‡. Motor must be converted to 115 VAC operation
• For altitudes above 2,000 feet, reduce capacity 4% for each 1,000 ft. above sea level. Refer to form 650.74-N1.1V
• Wire size based on copper conductors, 60_ C, 3% voltage drop.
• See Replacement Parts list for LP gas and High Altitude conversion kits. External filter kits (bottom and side) are also available for
models above.
• Continuous return air t temperature must not be below 55°F (13°C)
2
NOTE: Vent must be increased to 5" using adapter provided.
All dimensions are in inches and are approximate.
Output
Air Temp
*
AFUE
MBH
Rise °F
130
78
25 - 55
208/230 VAC (ONLY)
115 and 208/230 VAC (SPLIT)
115 VAC (ONLY)
Blower
Max.
HP
Nomi-
Outlet
nal
Temp.
Motor
°F
Amps
@230V
150
1-1/2
10
Max.
Size
Total
Over-
Unit
Current
Amps
Protect.
12 x 15
15
20
6 & 11
15
27
30
Unitary Products Group
Min. Wire
Oper.
Size (AWG)
Wgt.
@ 75 Ft.
(Lbs)
One Way
250
12
12
10

Advertisement

loading