Siemens SCOR Installation, Operation & Maintenance Instructions Manual page 25

Overcurrent protective relay
Table of Contents

Advertisement

4 Installation and Testing
4.7.4
Timing Test
The timing characteristics available by programming the relay
are illustrated in Figures A.1 through A.16. Output trip should
occur as shown for any given TIME DIAL setting, to within 1 0%
or 20 milliseconds (whichever is greater) . Verification of timing
accuracy can be limited to low current levels for convenience.
Verify timing accuracy as follows:
1 .
After performing the "Preliminary Steps" (Page 1 9), con­
nect the input current source to terminals 7 and 8 on the
relay case (Phase A).
2 .
Select the time overcurrent characteristic of choice by
entering its identifying code number into the Phase curve
(Pcur) register. (Reference Table 3.) Similarly load the
Ground curve register with the characteristic of choice (if
ground current monitoring is a relay option.)
3.
Set the PHASE TAP switch to position A. Load 99 into the
Time Dial register. (The Phase tAP calibrate register is still
at the 00 setting given in "Preliminary Steps. ")
4.
Measure the timing from the application of input current to
output contact closure for currents that are adjusted to the
following multiples of TAP:
a.
2.0 x TAP, and
b.
5.0 x TAP
Check the results against the graphed values.
5 .
Adjust the TIME DIAL t o 2 0 and repeat step 4 .
NOT E
If this is a single-phase relay, this concludes a minimal
Timing Test. Other TAP switch positions may be tried
within the limitations of the current source. If this is a
three-phase relay with ground, perform the following
steps.
BUS
52
-
LEGEND
51
A
B
C
52
LINE
Figure 1 2. Two-Phase with Residually Connected
Ground, Current Sensing Connections
6 .
Disconnect the input current source from terminals 7 and
8 (Phase A) and connect it to terminals 1 4 and 1 5 (Phase
B) .
Repeat steps 2 through 5 above for Phase B.
7.
8.
Disconnect the input current source from terminals 14 and
1 5 (Phase B) and connect it to terminals 1 7 and 1 8 (Phase
C).
9 .
Repeat steps 2 through 5 above for Phase C .
1 0. Disconnect the input current source from terminals 1 7 and
1 8 (Phase C) and connect it to terminals 1 3 and 1 6
(Ground).
Repeat steps 2 through 5 above for ground current.
1 1
.
Page 23
A
B
c
51
51
A
51
51
c
51
5 1
N
1 6
OVERCURRENT RELAY
POWER CIRCUIT BREAKER