The following table lists the data entry fields on the screen and a description of their purposes.
TERM
DEFINITION
CUT-IN
Cut-in Setpoint. If Automatic or Auto-Remote mode is
selected, Auto Start/Stop is enabled, the compressor is
on-line, and the suction pressure rises above the Cut-in
Setpoint, the compressor will start.
CONTROL
Control Setpoint. In the Automatic or Auto-Remote
mode of operation the compressor is loaded or unloaded
as required to maintain the Control Set-point.
CUT-OUT
Cut-out Setpoint. If Automatic or Auto-Remote mode
is selected, Auto Start/Stop is enabled, the compressor is
running, and the suction pressure falls below the Cut-out
Setpoint, the compressor will stop.
LOW ALARM
The Suction Pressure value at which the Viltech should
report a Low Suction Pressure alarm to the operator
(for all modes except Sequenced).
LOW FAILURE The Suction Pressure value at which the Viltech should
fail (stop) the compressor and report a failure to the
operator (for all modes except Sequenced).
62
Suction Pressure Control Data Definitions
Suction Pressure Active Group Control Screen
RANGE
29.9 INHG 185.0 PSIG
29.9 INHG 185.0 PSIG
29.9 INHG 185.0 PSIG
29.9 INHG 185.0 PSIG
29.9 INHG 185.0 PSIG