ABB REM615 List Manual page 27

Relion 615 series, motor protection and control rem615 ansi dnp3 point list manual
Hide thumbs Also See for REM615:
Table of Contents

Advertisement

1MAC254287-MB B
DNP
No
Point
Object
DNP Class
Event
Index
Type
BI
161
Class 1 and 0
BI
162
Class 1 and 0
BI
163
Class 1 and 0
BI
164
Class 1 and 0
AI
42
Class 2 and 0
AI
43
Class 2 and 0
AI
44
Class 2 and 0
AI
45
Class 2 and 0
AI
46
Class 2 and 0
AI
47
Class 2 and 0
DNP
No
Point
Object
DNP Class
Event
Index
Type
BI
Yes
165
Class 0
AI
Yes
48
Class 0
AI
Yes
49
Class 0
AI
Yes
50
Class 0
AI
Yes
51
Class 0
AI
Yes
52
Class 0
AI
Yes
53
Class 0
DNP
No
Point
Object
DNP Class
Event
Index
Type
BI
166
Class 1 and 0
BI
167
Class 1 and 0
BI
168
Class 1 and 0
BI
169
Class 1 and 0
AI
54
Class 2 and 0
AI
55
Class 2 and 0
AI
56
Class 2 and 0
REM615 ANSI
Point List Manual
Table 59:
A-IB-IC:Three-phase current measurement-instance 1 (CMMXU1)
Enabled Description
Yes
IA IB IC (1) Current Source High Alarm
Yes
IA IB IC (1) Current Source High
Warning
Yes
IA IB IC (1) Current Source Low Warning
Yes
IA IB IC (1) Current Source Low Alarm
Yes
IA IB IC (1) Phase A Mag (RMS)
Yes
IA IB IC (1) Phase A Mag
(Deadbanded)
Yes
IA IB IC (1) Phase B Mag (RMS)
Yes
IA IB IC (1) Phase B Mag
(Deadbanded)
Yes
IA IB IC (1) Phase C Mag (RMS)
Yes
IA IB IC (1) Phase C Mag
(Deadbanded)
Table 60:
IA-IB-IC:Three-phase current measurement-instance 1 (CMSTA1)
Enabled Description
Yes
IA IB IC (1) Reset Max Demands
Yes
IA IB IC (1) Phase A Average Demand
Yes
IA IB IC (1) Phase A Maximum Demand
Yes
IA IB IC (1) Phase B Average Demand
Yes
IA IB IC (1) Phase B Maximum Demand
Yes
IA IB IC (1) Phase C Average Demand
Yes
IA IB IC (1) Phase C Maximum Demand
Table 61:
IA-IB-IC (2):Three-phase current measurement-instance 2 (CMMXU2)
Enabled Description
Yes
IA IB IC (2) Current Source High Alarm
Yes
IA IB IC (2) Current Source High
Warning
Yes
IA IB IC (2) Current Source Low Warning
Yes
IA IB IC (2) Current Source Low Alarm
Yes
IA IB IC (2) Phase A Mag (RMS)
Yes
IA IB IC (2) Phase A Mag
(Deadbanded)
Yes
IA IB IC (2) Phase B Mag (RMS)
Section 2
DNP3 data mappings
Scale
IEC61850 Data Attribute Name
Factor
LD0.CMMXU1.HiAlm.stVal
LD0.CMMXU1.HiWrn.stVal
LD0.CMMXU1.LoWrn.stVal
LD0.CMMXU1.LoAlm.stVal
100
LD0.CMMXU1.A.phsA.instCVal.m
ag.f
100
LD0.CMMXU1.A.phsA.cVal.mag.f
100
LD0.CMMXU1.A.phsB.instCVal.m
ag.f
100
LD0.CMMXU1.A.phsB.cVal.mag.f
100
LD0.CMMXU1.A.phsC.instCVal.m
ag.f
100
LD0.CMMXU1.A.phsC.cVal.mag.f
Scale
IEC61850 Data Attribute Name
Factor
LD0.CMSTA1.RecRs.stVal
100
LD0.CMSTA1.AvAmpsA.mag.f
100
LD0.CMSTA1.MaxAmpsA.mag.f
100
LD0.CMSTA1.AvAmpsB.mag.f
100
LD0.CMSTA1.MaxAmpsB.mag.f
100
LD0.CMSTA1.AvAmpsC.mag.f
100
LD0.CMSTA1.MaxAmpsC.mag.f
Scale
IEC61850 Data Attribute Name
Factor
LD0.CMMXU2.HiAlm.stVal
LD0.CMMXU2.HiWrn.stVal
LD0.CMMXU2.LoWrn.stVal
LD0.CMMXU2.LoAlm.stVal
100
LD0.CMMXU2.A.phsA.instCVal.m
ag.f
100
LD0.CMMXU2.A.phsA.cVal.mag.f
100
LD0.CMMXU2.A.phsB.instCVal.m
ag.f
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents