Packing And Transport - ABB VD4 12 Installation And Service Instructions Manual

Vd4 series 12 - 24 kv; 630 - 2500 a; 16 - 31.5 ka
Table of Contents

Advertisement

Caption
A Circuit-breaker rating
plate.
B Operating mechanism
rating plate.
1 Type of apparatus.
2 Symbols of compliance
with Standards.
3 Serial number.
4 Circuit-breaker charac-
teristics.
5 Characteristics of the
operating mechanism
auxiliaries.
Fig. 1
4
1.

Packing and transport

The circuit-breaker is shipped in special pack-
ing, in the open position and with the springs
discharged.
Each piece of apparatus is protected by a plas-
tic cover to prevent any infiltration of water dur-
ing the loading and unloading stages and to keep
the dust off during storage.
2.
Checking on receipt
Before carrying out any operation, al-
!
ways make sure that the operating
mechanism springs are discharged
and that the apparatus is in the open
position.
On receipt, check the state of the apparatus,
integrity of the packing and correspondence with
the nameplate data (see fig. 1) with what is speci-
fied in the order confirmation and in the accom-
panying shipping note.
Also make sure that all the materials described
in the shipping note are included in the supply.
1
A
CIRCUIT-BREAKER
VD4 ...
3
NO. ...
RATED VOLTAGE
IMPULSE WITHSTAND VOLTAGE ATM.
RATED FREQUENCY
RATED NORMAL CURRENT
4
SHORT-TIME CURRENT
CLOSING / OPENING TIME
BREAKING CAPACITY
MAKING CAPACITY
AT A VOLTAGE OF
OPERATION SEQUENCE
B
OPERATING MECHANISM
EL ...
NO. ...
– MO
– MO1
5
– MS
Designed and manufactured by ABB
Should any damage or irregularity be noted in
the supply on unpacking, notify ABB (directly or
through the agent or supplier) as soon as possi-
ble and in any case within five days of receipt.
The apparatus is only supplied with the acces-
sories specified at the time of ordering and vali-
dated in the order confirmation sent by ABB.
The accompanying documents inserted in the
shipping packing are:
– instruction manual (this document)
– test certification
– identification label
– copy of the shipping document
– electric wiring diagram.
Other documents which are sent prior to ship-
ment of the apparatus are:
– order confirmation
– original shipping advice notes
– any drawings or documents referring to spe-
cial configurations/conditions.
3.
When a period of storage is foreseen, our work-
shops can (on request) provide suitable packing
for the specified storage conditions.
On receipt the apparatus must be carefully un-
packed and checked as described in Checking
2
on receipt (chap. 2).
If immediate installation is not possible, the
IEC 62271-100
CEI 17-1
packing must be replaced, using the original
material supplied.
MASSE
... kg
... kV
Insert hygroscopic packets inside the packing,
... kV
50/60Hz
with at least one standard packet for piece of
...
A
(...s)
... kA
apparatus.
... ms
... kA
Should the original packing not be available and
... kA
... kV
immediate installation is not possible, store in a
O-0,3s-CO-3Min-CO
covered, well-ventilated, dry, dust-free, non-cor-
rosive ambient, away from any flammable mate-
IEC 62271-100
rials and at a temperature between –5 °C and
CEI 17-1
+45 °C.
In any case, avoid any accidental impacts or
...
V ...
...
V ...
positioning which stresses the structure of the
apparatus.
...
V ...
Storage

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vd4 17Vd4 24

Table of Contents