1. Installation

1-1 Refrigerant Refill Procedure
Refill an air-conditioner with refrigerant when refrigerant has been leaked at installing or using
1. Purge air(for new installation only).
2. Turn the 3-way valve clockwise to close, connect the
pressure gauge(low pressure side) to the service valve,
and open the 3-way valve again.
3. Connect the tank to refill with Refrigerant
4. Set the unit to cool operation mode.
5. Check the pressure indicated by the pressure gauge(low
pressure side).
* Standard pressure is should be 4.5~5.5kg/cm
regular, high operation mode.
6. Open the refrigerant tank and fill with refrigerant until
the rated pressure is reached.
* It is recommended not to pour the refrigerant in too
quickly, but gradually while operating a pressure valve.
7. Stop operation of the air conditioner.
8. Close the 3-way valve, disconnect the pressure gauge,
and open the 3-way valve again.
9. Close the cap of each valve.
2
in a
Compound
gauge
For mounting
other and of
hose when
not in use
Suspension hook
High
pressure
gauge
Hand
wheel
Finger tight
fittings
Connected to
high pressure
side
Charging
line
1