UPS Connections (Cont'd)
5.3
Terminal Block details (Cont'd)
5.3.2
UPS model numbers UC1G2L024C6TB
The following illustration is a detail of the UPS unit's terminal block (see Section
9.1 for terminal block location).
Notes:
1) If ac input power is 208 Vac rated, terminals 11 and 12 must be shorted by a jumper
wire.
Do not jumper terminal 13 to either 12 or 11.
Factory setting is 208 Vac.
2) If ac input power is 240 Vac rated, terminals 12 and 13 must be shorted by a jumper
wire.
Do not jumper terminal 11 to either 12 or 13.