Item
Voltage class
Frame size
Applicable motor (kW)
Applicable motor (HP)
Type
Form
Output capacity (kVA)
Output current (A)
Output voltage
Overload current rating
Dynamic braking circuit
Dynamic braking resistor
Voltage-frequency

Allowable fluctuation
Required power supply
*4
capacity (kVA)

Degree of protection (IEC60529)
Enclosure rating (UL50)

Cooling method
Cooling fan noise (dBA)
*6
Reference value
Color
EMC filter
DC reactor
*1. Capacity is calculated at 440 V for the 480 V class.
*2. Indicates rated output current setting when the PWM carrier frequency (parameter F300) is 4 kHz.

*3. Lower limit of voltage for 480 V class is 342 V when the inverter is used continuously (load of 100%).
*4. Required power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and wires).
*5. The top cover included in the package must be installed with inverter, it is Type1 without the top cover.
*6. These acoustic noise values are not guaranteed because they are just reference values.
6. Specifications
22
30
4220PCE
4300PCE
*1
35.3
*2
46.3
3-phase 380 V to 480 V (The maximum output voltage is equal to the input supply voltage)
32.7
Specification
480 V class
A4E
30
37
40
50
VFAS3-
4370PCE
4450PCE
46.9
56.8
61.5
74.5
150%-1 minute, 180%-2 s
Built-in
External braking resistor (Optional)
3-phase 380 V to 480 V - 50/60 Hz
*3
Voltage 323 V to 528 V
, Frequency ± 5%
44.3
53.9
IP55
*5
Type 12
Forced air-cooled
64
RAL7016
Built-in
Built-in
6-2
E6582162c
A5E
45
55
60
75
4550PCE
4750PCE
67.1
80.8
88.0
106
65.6
79.5
63
75
100
111
145
108