ABB ACS800 Hardware Manual page 68

45 / 60 to 560 / 600 kw
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

68
Connecting the power cables of units with EMC filter +E202. Frame size R7 with bottom entry and exit.
Step
Instruction
3
Cut an adequate hole to the rubber grommet in the lead-through plate and lead the motor cable through the
grommet and the conductive sleeve into the cabinet.
4
Peel off 3 to 5 cm of the outer insulation of the cable above the lead-through plate for the 360° high-frequency
earthing.
5
Fasten the conductive sleeve to the cable shield with cable ties.
6
Tie up the unused conductive sleeves with cable ties.
7
Connect the twisted shield of the motor cable to the PE busbar of the cabinet.
8
Connect the phase conductors of the motor cable to the U2, V2 and W2 terminals.
9
If optional brake chopper is included, lead the brake resistor cable into the cubicle as described above. Connect the
brake resistor conductors to the R+ and R- terminals and the twisted shield to the PE busbar.
10
Fasten the EMC screen. See the photo on the previous page.
Cable shield
PE busbar
7
Strip this part
4
of the cable
Base plate
Lead-through plate
Installation
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
EMC sleeve
5
6
Photo
U1
INPUT
8
OUTPUT
6
V1
W1
8
8
7
PE
3
Connecting the
motor cable

Hide quick links: