E2S D1xL1-V070-D Instruction And Service Manual

D1xl1 / d1xl2 series, for use in hazardous locations – dust

Advertisement

Quick Links

The D1xL1 & D1xL2 Loudspeakers are certified
by UL as Audible-signal Appliances for Use in
Hazardous Locations
1)
Introduction
The D1xL1 & D1xL2 are UL certified loudspeakers which
produce a loud warning signal in a hazardous area. The
loudspeaker are approved for use in Dust applications in Class
II Division 1 & 2 as well as Class II Division 1 & 2 and Class III
Division 1 & 2 as well as Class II Zone 20, 21 and 22.
D1xS1 & D1xS2 alarm horns and D1xC1 & D1xC2 Combined
alarm horn & Strobe are also available as well as variants for
Explosive Dust Atmospheres.
2)
Warnings
CAUTION
TO REDUCE THE RISK OF IGNITION OF HAZARDOUS
ATMOSPHERES:
DISCONNECT FROM SUPPLY BEFORE OPENING.
KEEP TIGHTLY CLOSED WHEN IN OPERATION.
WARNING
FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18
INCHES FROM ENCLOSURE.
EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN
FACING UPWARDS OF HORIZONTAL
ATTENTION
POUR REDUIRE LE RISQUE D'INFLAMMATION DES
ATMOSPHÈRES DANGEREUSES:
COUPER L 'ALIMENTATION AVANT OUVERTURE.
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT.
AVERTISSEMENT
CONDUITS DOIVENT ÊTRE SCELLÉS EN MOINS DE 18
POUCES.
ÉQUIPEMENT NE DOIT PAS ÊTRE INSTALLÉ AVEC LE
KLAXON TOURNÉE VERS LE HAUT DE HORIZONTAL.
__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D190-00-251-IS-SC
INSTRUCTION & SERVICE MANUAL
D1xL1 & D1xL2 LOUDSPEAKER
For Use In Hazardous Locations – Dust
Issue: 4
27-08-15
3)
Ratings and Markings
3.1 Class / Division Ratings for US and Canada
The D1x Loudspeakers comply with the following standards for
hazardous locations:
UL 1203
CAN/CSA C22.2 No. 25-1966
The D1xL1 & D1xL2 Loudspeakers also comply with the
following standards for signaling equipment:
UL1480
CSA C22.2 NO. 205-12
3.1 Class / Division Ratings for US & Canada
Class II Div 1
FG
Class III Div 1
Installation must be carried out in compliance with the National
Electric Code / Canadian Electric Code
3.2 Class / Zone ratings for US and Canada
Zone 20 IIC
T6
Installation must be carried out in compliance with the National
Electric Code / Canadian Electric Code.
3.3 Ambient Temperature Range:
-40ºC to +70ºC
3.4 Enclosure Ratings
The product is rated for ingress protection as follows:
IP rating per EN60529:
Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13
3.5 Electrical Ratings
Model No.
Input
D1xL1-V070-D
70V Line
D1xL1-R008-D
8 Ohm
D1xL1-R016-D
16 Ohm
D1xL2-V070-D
70V Line
D1xL2-R008-D
8 Ohm
D1xL2-R016-D
16 Ohm
3.6 Frequency Range
All models: 400Hz to 8000 Hz
4)
Installation
4.1 Safe Installation Requirements
The product must only be installed by suitably qualified
personnel in accordance with the latest issues of the relevant
standards.
sales@e-2-s.com
www.e-2-s.com
Sheet 1 of 3
T6
Ta -40°C to +70°C
Ta -40°C to +70°C
Ta -40ºC to +70°C
IP66
Power
Max I/P
(Watts)
Volts
15
70
15
10.95
15
15.49
25
70
25
14.14
25
20
Tel: +44 (0)208 743 8880
Fax: +44 (0)208 740 4200

Advertisement

loading

Summary of Contents for E2S D1xL1-V070-D

  • Page 1 3.5 Electrical Ratings FACING UPWARDS OF HORIZONTAL Model No. Input Power Max I/P ATTENTION (Watts) Volts POUR REDUIRE LE RISQUE D’INFLAMMATION DES D1xL1-V070-D 70V Line ATMOSPHÈRES DANGEREUSES: D1xL1-R008-D 8 Ohm 10.95 COUPER L 'ALIMENTATION AVANT OUVERTURE. D1xL1-R016-D 16 Ohm 15.49 CONSERVER FERMÉ...
  • Page 2 power supply terminals on the low impedance units are The installation of the units must also be in accordance with the duplicated so that units may be connected in parallel. An NEC / CEC and any local regulations and should only be carried end of line monitoring resistor may be fitted to either type out by a competent electrical engineer who has the necessary of unit.
  • Page 3 The cable connections are made into the terminal blocks on the End of Line DC Monitoring PCB assembly located in the explosionproof enclosure. See section 5 of this manual for access to the explosionproof On D1xL2 and D1xL1 Loudspeakers, DC line monitoring can be enclosure.