Samsung ACH1800E Technical Manual page 29

Hide thumbs Also See for ACH1800E:
Table of Contents

Advertisement

3
INSTALLATION
Operation of the Remote Controller
3-1-6. The Indicator on the Receive & Display Unit
Duct Type
Remote control sensor
3-1-7. Operation specification of wireless receiving board
PART NAME
DEFROST LAMP
FILTER SIGN LAMP
TIMER LAMP
ON-OFF LAMP
ON-OFF BUTTON
3-1-8. Wireless receiving board and outdoor unit PCB display specification when error occurs
ERROR
MODE
Abnormal on indoor temperature sensor
E1
(4.9[V] and higher, 0.5[V] and lower
Abnormal on indoor pipe temperature sensor
E5
(4.9[V] and higher, 0.5[V] and lower
Abnormal on outdoor temperature sensor
E6
(4.9[V] and higher, 0.5[V] and lower
Float switch detection
E9
Indoor ↔ outdoor communication defect
EA
Indoor unit ↔ wired remote controller
EC
communication defect
Abnormal on outdoor pipe temperature sensor
Ed
(4.9[V] and higher, 0.5[V] and lower
28 | SAMSUNG
Timer indicator
On/Off indicator
SOURCE & OPERATION SPEC.
RED, lamp on during defrost operation
Green, display during filter cleaning
Green, lamp when setting the reserve operation
Red, lamp during operation on
On/Off toggle operation
CONTENTS OF ERROR
(Cont.)
Removing frost indicator
Filter Sign indicator
On/Off button
in ERROR DISPLAY : flickering
in ERROR DISPLAY : flickering
in ERROR DISPLAY : flickering
in ERROR DISPLAY : flickering
Operated only for automatic mode operation
WIRELESS RECEIVING
BOARD
Reservation LED flickering
(1Hz period)
Operation LED and reservation
LED flickering (1Hz period)
Operation LED and filter LED
flickering (1Hz period)
Reservation LED and filter LED
alternating flickering (1Hz period)
Reservation LED and filter LED
flickering (1Hz period)
Operation LED and reservation
LED alternating flickering (1Hz
period)
Filter LED flickering (1Hz period)
REMARK
REMARK
Restored when the indoor tem-
perature sensor is normal
Restored when the indoor pipe
temperature sensor is normal
Restored when the outdoor
temperature sensor is normal
Float switch detection
Re-detecting by operating off
signal after restoring
Restored when outdoor pipe
temperature sensor is normal

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents