Econopak water heaters type wh
Table of Contents

Advertisement

2. Attach mounting angles to heater jacket with 1/2"
sheet metal screws, (4 places).
Fig. 4: Location of Mounting Angles
3. Lower outdoor top to heater and secure with 1"
sheet metal screws.
Fig. 5: Long Side of Mounting Angle Located as Shown
Indoor Models
The drafthood is shipped separately and must be
installed on the heater.
Models 0260 & 0261
1. Mount drafthood on top of heater and attach with
the 4 sheet metal screws provided. Drafthood
should be positioned with the vent sensor located
on the front left side as shown.
2. Remove plastic plug from left side of heater jacket
and install plastic grommet provided.
3. Route flue sensor wire harness through the grom-
met installed in Step 2.
CONNECT ONE
VENT SENSOR
WIRE TO THE
HIGH LIMIT WIRE
CONNECT ONE
VENT SENSOR
WIRE TO THE
ROLL-OUT
SENSOR WIRE
WIRE FROM
TRANSFORMER
ROLL-OUT
SENSOR
Fig. 6: Mounting Flue Sensor
4. Remove door and locate wire from roll out sensor
to Hi Limit with the male/female connector.
Fig. 7: Before Installation of Drafthood
Fig. 8: After Installation of Drafthood
5. Disconnect male/female connector and attach to
the 2 wires from drafthood vent sensor harness.
10
TEMPERATURE
SENSOR
MOUNTING
SCREWS (2)
HARNESS
ASSEMBLY
WIRE FROM TRANSFORMER
MALE/FEMALE
WIRE TERMINAL
WIRE FROM HIGH LIMIT
ROLL OUT SENSOR
WIRE FROM TRANSFORMER
CONNECT ONE VENT SENSOR WIRE
TO HIGH LIMIT WIRE
CONNECT ONE VENT SENSOR WIRE
TO ROLL OUT SENSOR WIRE
ROLL OUT SENSOR