Section H - Raypak 122-322 Operating And Installation Instructions

Type h, wh, & p hi delta 122; 162; 202; 242; 322
Table of Contents

Advertisement

SECTION H: GAS SUPPLY CONNECTIONS
DANGER:
Make sure the gas on which the heater will operate is the same type as specified on the heater model and
rating plate.
Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut-off valve located outside the
heater jacket. A pounds to inches regulator must be installed to reduce to gas supply pressure to under 14" W.C. The
regulator should be placed a minimum distance of 10 times the pipe diameter upstream of the heater gas controls. All gas
piping must be tested after installation in accordance with local codes. The heater and its gas connection must be leak-tested
before placing it in operation.
GAS SUPPLY CONNECTION
CAUTION:
The heater and its manual shutoff valve must be disconnected from the gas supply during any pressure
testing of the gas supply system at test pressures in excess of 1/2 PSIG (3.45 KPA). The heater must be
isolated from the gas supply piping system by closing the manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG. Relieve test
pressure in the gas supply line before reconnecting the heater and its manual shut off valve to the gas
supply line. FAILURE TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVES. Over
pressurized gas valves are not covered by warranty. The heater and its gas connections shall be leak
tested before placing the appliance in operation. Use soapy water for leak test: DO NOT use open flame.
CAUTION:
Do not use Teflon tape on gas line pipe thread. A pipe compound rated for use with gas systems is
recommended. Apply sparingly only on male pipe ends.
CAUTION:
Support gas supply piping with hangers, not by the heater or its accessories. Ensure the gas piping is
protected from physical damage and freezing where required.
GAS SUPPLY PRESSURE
A minimum of 7" W.C. and a maximum of 10.5" W.C. upstream gas pressure is required under no load conditions for natural
gas. A minimum of 12" W.C. and a maximum of 13" W.C. is required for propane gas. The gas pressure regulator supplied on
the heater is for low pressure service. If upstream pressure exceeds 14" W.C, an intermediate gas pressure regulator, of
the lockup type, must be installed.
When connecting additional gas utilization equipment to the gas piping system, the existing piping must be checked to
determine if it has adequate capacity.
19
Fig. #9401.1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents