Advertisement

Load
UPS5000 battery
(hours:minutes)
50 W
6:49
100 W
4:50
200 W
3:00
300 W
2:09
400 W
1:39
500 W
1:20
600 W
1:07
700 W
0:57
800 W
0:50
900 W
0:44
1000 W
0:39
1200 W
0:32
1400 W
0:26
1600 W
0:22
1800 W
0:19
2000 W
0:17
2500 W
0:12
3000 W
0:09
3400 W
0:07
4000 W
0:06
4500 W
0:05
Table 3 lists the number of hours needed to recharge the IBM UPS5000 HV uninterruptible power supply
and optional Online Battery Packs.
Table 3. Recharge times
UPS5000 battery With 1 OBP
Recharge time
3 hours

Related publications

IBM UPS5000 HV Uninterruptible Power Supply for IBM System x
With 1 OBP
With 2 OBPs
(hours:minutes)
(hours:minutes)
18:03
31:32
12:51
22:29
8:03
14:06
5:47
10:10
4:30
7:54
3:39
6:26
3:04
5:24
2:38
4:39
2:18
4:04
2:02
3:37
1:50
3:15
1:30
2:41
1:16
2:17
1:06
1:59
0:58
1:45
0:52
1:33
0:40
1:13
0:32
1:00
0:25
0:50
0:23
0:43
0:20
0:38
With 2 OBPs
9 hours
15 hours
With 3 OBPs
With 4 OBPs
(hours:minutes)
(hours:minutes)
45:33
59:56
32:30
42:46
20:23
26:50
14:42
19:22
11:26
15:04
9:19
12:17
7:50
10:20
6:45
8:54
5:55
7:48
5:15
6:56
4:43
6:14
3:55
5:11
3:20
4:25
2:54
3:50
2:33
3:23
2:17
3:01
1:47
2:22
1:28
1:57
1:12
1:40
1:00
1:25
0:54
1:15
With 3 OBPs
With 4 OBPs
21 hours
27 hours
10