PART 1 - GENERAL
1.1
SUMMARY
A. Section includes gas-fired, copper finned-tube hydronic heating boilers
B. Related Sections
Specifier Note: Use as needed
1. Building Services Piping – Division 23 21 00
2. Breeching, Chimneys, and Stacks (Venting) – Division 23 51 00
3. HVAC Instrumentation and Controls – Division 23 09 00
4. Electrical – Division 23 09 33
1.2
REFERENCES
A. ANSI Z21.13/CSA 4.9
B. ASME, BPV Section IV
C. 2006 UMC, Section 1107.6
D. ANSI/ASHRAE 15-1994, Section 8.13.6
E. National Fuel Gas Code, ANSI Z223.1/NFPA 54
F. I=B=R
G. National Electrical Code. ANSI/NFPA 70
H. ASME CSD-1, 2009 (when required)
1.3
SUBMITTALS
A. Product data sheet (including dimensions, rated capacities, shipping weights, accessories)
B. Wiring diagram
C. Warranty information
D. Installation and operating instructions
1.4
QUALITY ASSURANCE
A. Regulatory Requirements
1. ANSI Z21.13/CSA 4.9
2. Local and national air quality regulations for low NOx (< 20 PPM NOx emissions) boilers
B. Certifications
1. CSA
2. ASME H Stamp and National Board Listed
3. ISO 9001
1.5
WARRANTY
A. Limited one-year warranty from date of installation
B. Limited twenty-year thermal shock warranty
C. Limited ten-year closed-system heat exchanger warranty
PART 2 - PRODUCTS
2.1
MANUFACTURER
A. Raypak, Inc.
1. Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300;
Project Name / Date
®
HI DELTA
, TYPE H - MODELS 992BE-2342BE
SUGGESTED SPECIFICATIONS
DIVISION 23 52 33.13
FINNED WATER-TUBE BOILERS
Catalog No.: 2000.952D
Effective:
9-1-09
Replaces:
5-1-08
Division 23 52 33.13 - 1

Advertisement

loading

Summary of Contents for Raypak 2342BE

  • Page 1 PART 2 - PRODUCTS MANUFACTURER A. Raypak, Inc. 1. Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300; Project Name / Date ® , TYPE H - MODELS 992BE-2342BE SUGGESTED SPECIFICATIONS DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS Catalog No.: 2000.952D Effective:...
  • Page 2 A. General 1. The boiler(s) shall be fired with 2. The boiler(s) shall be CSA tested and certified with a minimum thermal efficiency of 87 percent at full fire. 3. The boiler(s) shall be ASME inspected and stamped and National Board registered for 160 PSIG working pressure, complete with a Manufacturer's Data Report.
  • Page 3 G. Firing Mode 1. For models 992BE, provide three-stage firing control of the gas input to the boiler. 2. For models 1262BE-2342BE, provide four-stage firing control of the gas input to the boiler. H. Boiler Diagnostics 1. Provide external LED panel displaying the following boiler status/faults: a.
  • Page 4 2. The boiler(s), if located on a combustible floor, shall not require a separate combustible floor base. 3. The boiler(s) shall have the option of venting the flue products either through the top or the back of the unit. 4. Combustion air intake shall be on the left side of the cabinet, right side optional.
  • Page 5 Sensor out of range 6. The controller shall have alarm contacts. Q. Low Gas Supply Pressure Manifold 1. The boiler(s) shall be CSA certified for full-input operation down to 4.0” WC dynamic inlet gas supply pressure. R. TruSeal™ Direct Vent 1.