WIRINg

1. Unscrew the cover. (rotate counterclockwise)
2. LCD unit is attached, remove it. (Rotate counterclockwise or to OPEN)
3. Open the wire entry of terminal block by pushing on the actuating lever with a flat screwdriver
4. Insert wires as shown on the panel (positive (+) to terminal entry No. 1 and negative (-) to terminal No. 2)
5. Release actuating lever of the terminal
6. Connect the ground wire to internal earth ground terminal (D-Class grounding).
7. Attach the LCD unit if it had been installed
8. Screw the cover on tightly
9. Connect ground screw (D-Class grounding) between conduit entry to tank or any other earth ground.
CAUTION: dO NOT CONNECT CABlE SHIEld WIRE ON dEVICE RECEIVINg 4-20mA SIgNAl.
The LCD Adjustment
Unit removed
MPR180213 Rev. B
Do not touch the LCD Adjustment Unit connection
terminal while instrument is powered on.
Power Supply
24 VDC
(D-class grounding) M4
Customer Supplied
Display/
Input
+
+
7
www.bindicator.com