Auxiliary Contact - Generac Power Systems RXSW200A3F Owner's Manual

Automatic transfer switch 200 amp, single phase, 240 vac, service rated, 8-16 circuit load center
Table of Contents

Advertisement

Installation
C
D
E
F

Auxiliary Contact

See
Figure
2-5. If desired, there is one normally-closed
Auxiliary Contact (A) on the transfer switch to operate
customer accessories, remote advisory lights, or remote
annunciator devices. A suitable power source must be
connected to the common terminal. If needed, an extra
auxiliary contact can be added.
The auxiliary contact is normally closed when the transfer
switch is in utility mode. The contacts will open when the
transfer switch is in the standby power mode.
NOTE: Auxiliary Contact is rated 10 amps at 125 or 250
volts AC, and 0.6 amps at 125 volts DC.
CAUTION
Equipment damage. Exceeding rated voltage and
current will damage the auxiliary contacts. Verify
that voltage and current are within specification
before energizing this equipment.
8
A
B
G
H
J
Figure 2-4. Typical SACM Connections
(000134a)
1
2
1
2
1
2
1
2
T1
N1
N2
T1
0
N1
N2
194
0 GROUND
194 +12V
23
23 TRANSFER
Replace with Littlefuse 021606.3MXHP,
®
Optifuse FCD-6.3A or
®
Generac 10000005117 250 vac, 6.3A
N2
N1
T1
004435
Figure 2-5. Auxiliary Contact
Automatic Transfer Switch Owner's Manual
A—Thermostat 1
B—Air Conditioner 1
C—Thermostat 2
D—Air Conditioner 2
E—Thermostat 3
F—Air Conditioner 3
G—Thermostat 4
H—Air Conditioner 4
T1 (fused)—Battery Charge
(blue background, white letters)
N1 (fused)—Utility Sense
(yellow background, black letters)
N2 (fused)—Utility Sense
(yellow background with black
stripe, black letters)
0—Ground
(black background, white
letters)
194— +12 VDC
(red background, white letters)
23—Transfer Control
(white background, black
letters)
J—240 VAC, 6.3A Fuses