ABB REM 610 Product Manual page 8

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

Technical data (cont´d)
8
Motor Protection Relay
Table 11: RTD/analogue inputs
Supported RTD sensors
Supported PTC thermistor range
Maximum lead resistance (three-wire measurement)
Isolation
Sampling frequency
Response time
RTD/Resistance sensing current
Table 12: Environmental tests and conditions
Recommended service temperature range (continuous)
Limit temperature range (short-term)
Transport and storage temperature range
Dry heat test
Dry cold test
Damp heat test, cyclic
Table 13: Electromagnetic compatibility tests
EMC immunity test level meets the requirements listed below:
1 MHz burst disturbance test, class III:
- common mode
- differential mode
Electrostatic discharge test, class IV:
- for contact discharge
- for air discharge
Radio frequency interference tests:
- conducted, common mode
- radiated, amplitude-modulated
- radiated, pulse-modulated
Fast transient disturbance tests:
• power outputs, energizing inputs, power supply
• I/O ports
Surge immunity test:
• Power outputs, energizing inputs, power supply
• I/O ports
Power frequency (50 Hz) magnetic field
IEC 61000-4-8
1MRS 755121
100 Ω platinum
TCR0.00385
(DIN 43760)
250 Ω platinum
TCR 0.00385
1000 Ω platinum
TCR 0.00385
100 Ω nickel
TCR 0.00618
(DIN 43760)
120 Ω nickel
TCR 0.00618
120 Ω nickel (US)
TCR 0.00672
10 Ω copper
TCR 0.00427
0...20 kΩ
200 Ω per lead
2 kV (inputs to protective earth)
5 Hz
<8 s
Maximum 4.2 mA rms
6.2 mA rms for 10 Ω copper
-10...+55°C
-40...+70°C
-40...+85°C according to
the IEC 60068-2-48
According to the IEC 60068-2-2
According to the IEC 60068-2-1
According to the IEC 60068-2-30
According to the IEC 60255-22-1
2.5 kV
1.0 kV
According to the IEC 61000-4-2,
IEC 60255-22-2 and
ANSI C37.90.3-2001
8 kV
15 kV
According to the IEC 61000-4-6 and
IEC 60255-22-6 (2000)
10 V (rms), f=150 kHz...80 MHz
According to the IEC 61000-4-3 and
IEC 60255-22-3 (2000)
10 V/m (rms), f=80...1000 MHz
According to the ENV 50204 and
IEC 60255-22-3 (2000)
10 V/m, f=900 MHz
According to the IEC 60255-22-4 and
IEC 61000-4-4
4 kV
2 kV
According to the IEC 61000-4-5
4 kV, line-to-earth
2 kV, line-to-line
2 kV, line-to-earth
1 kV, line-to-line
300 A/m continuous
REM 610

Advertisement

Table of Contents
loading

Table of Contents