Hearth And Fire Surround; Preparation Of Fireplace; Connecting The Fans - Bay 5 Operating & Installation Instructions Manual

Charnwood
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS
chimney then a draught stabiliser should be fitted. If in doubt about
the chimney seek expert advice.

HEARTH AND FIRE SURROUND

The stove must be installed above a fireproof hearth of minimum
250mm depth in accordance with local building regulations, but
ideally 580mm deep to match the projection of the open door. The
positioning of the stove and the size of the hearth
building regulations for solid fuel appliances. If in doubt as to the
positioning of the stove expert advice should be sought either from
the supplier or the local building inspector.
If a wooden mantelpiece or beam is used in the fireplace it should be
a minimum of dimension 'D' from the appliance. In some situations it
may be necessary to shield the beam or mantelpiece to protect it.
In order for the appliance to fit into the fire surround there must be a
flat area around the opening. Details are shown in Fig. 10 & 12.

PREPARATION OF FIREPLACE

If the fireplace contains combustible materials, two air vents of 80mm
Fig. 10 Minimum Distances from Combustibles
C
A
From centre of
glass into room
B
Bay 5 & VL
Dimension A: 190mm
Dimension B: 250mm
Dimension C: 900mm
Dimension D: 350mm
(Bay 5 & VL) or 100mm (Bay 5GT) diameter must be fitted through
the insulation and the wall of the fireplace to provide a continual air
flow around the stove. Similar vents must be placed between the
closure plate and the top of the stove to ventilate the cavity. It is
recommended that Calcium Silicate board is used (80mm board for
Bay 5 & VL, 100mm board for Bay 5GT), with a 100mm air gap
between the stove and the insulation (see Fig. 11).
are governed by
Mantelpiece
D
A
Hearth
Bay 5GT
150mm
250mm
1000mm
460mm
If the fireplace does not contain combustible materials, it is still
recommended to have a layer of insulation or ventilate the space
between the casing and the outer wall. The insulation may consist of a
layer of mineral fibre or a vermiculite concrete mix (see Step 4). If
rockwool is being used, insert this into the opening before sliding in
the convection casing.
Before fitting the appliance into an existing fireplace remove the
fireback and any loose in-fill material.
The surround and opening for the appliance must conform with
Fig.12. The flat area around the opening should be a minimum of
700mm wide and 600mm high. Ensure that the hearth and the base
in the opening are flat, level, and at right angles to the surround.
For the Bay 5GT, consider where the low voltage power supply for
the fans is to be situated, and install electrical conduit from that point
to back left of the convection casing.
CONNECTING THE FANS (BAY 5GT ONLY)
The adaptor provided must be connected to a suitable mains socket.
Fig. 11 Air vents and insulation in a fireplace containing combustible
materials
Air vent through insulation and
wall of fireplace (Two on each side)
Calcium silicate board
80mm for Bay 5 & VL
100mm for Bay 5GT
Fig. 12 Limiting Dimensions of Surround and Opening
The shaded grey area on the face of the surround is
the minimum flat area required for inset installation.
Dimension A:
Bay 5 & VL
Min. 615mm
Max. 650mm
Min. 620mm
Bay 5GT
Max 650mm
12
charnwood
BAY
Ø80mm for Bay 5&VL
Ø100mm for Bay 5GT
100mm air gap
Top of stove
Fireplace
(Non-combustible)
700mm
A
600mm
B
C
Dimension B:
Dimension C:
Min. 410mm
Min. 380mm
Max. 440mm
Min. 510mm
Min. 400mm
Max. 540mm
®

Advertisement

Table of Contents
loading

This manual is also suitable for:

5vl5gt

Table of Contents