Commissioning
Enable blocking object
Options:
A 1-bit object to block temperature control can be enabled with this object. If temperature control is
blocked, the output object is no longer changed until the block is canceled, even if the temperature
exceeds/falls below the parameterized setpoint temperature.
62 2CDC509082D0201 | TR/A 1.1
No
Yes
No: The blocking object is deactivated.
Yes: The blocking object Temperature control blocking object – Reception is enabled.
The following dependent parameters are additionally enabled.
Evaluation of the blocking object
Options:
Block on 1
Block on 0
This parameter is used to set the condition under which temperature control is blocked.
Block on 1: Temperature control is blocked when a 1 is received on the input object.
A 0 cancels the block again.
Block on 0: Temperature control is blocked when a 0 is received on the input object.
A 1 cancels the block again.
State after reset
Options:
Enabled
Blocked
The parameter is used to define whether temperature control is to be blocked or enabled after an
ETS reset.
Enabled: Temperature control is enabled after ETS reset.
Blocked: Temperature control is blocked after ETS reset.