Error code
Error code (hexadecimal)
Description
100H
The set value of i_uAxis (Target axis) is out of range.
The target axis is not within the range of 1 to 12.
200H
The set value of i_uStartNo (Cd.3: Positioning start No.) is out of
range.
The positioning start No. is not within the range of 1 to 100.
201H
Positioning has been activated for the target axis.
Positioning error code
This is the same as the error code that occurs in the multiple table
operation (DRVTBL) instruction.
Self-diagnostics error
This may occur in the multiple table operation (DRVTBL)
instruction.
*1 When the same self-diagnosis error as another instruction occurs in this FB, this FB may not detect the error.
*1
Action
Try again after checking the setting.
Review the system configuration, servo amplifier
parameters and wiring, and then execute the FB
again.
Try executing the FB again after stopping activation of
the target axis.
Refer to the MELSEC iQ-F FX5 User's Manual
(Positioning Control - CPU module built-in, High-
speed pulse input/output module).
Refer to the MELSEC iQ-F FX5 User's Manual
(Application).
3 POSITIONING FB
3.2 M+FX5UCPU-Positioning_StartPositioning