23 Wiring diagram — WMB-80/120H Heating Only Ladder
Figure 70
WMB-80/120H –– Heating Only Ladder Wiring Diagram
NOTES:
1.
All wiring must be installed in
accordance with N.E.C. and
any other national state or local
requirements.
2.
Room thermostat should be a
dry contact type and should draw
power from the control board:
should not be greater than 24
VAC and 500 mA.
3.
Max. voltage and electric cur-
rent for the LWCO should not be
greater than 120VAC and 3 Amp.
4.
In case of questions during instal-
lation please contact your local
Weil-McLain distributor.
Legend
16
Fan
32
Central heating pump
42
DHW temperature sensor
44
Gas valve
72
Room thermostat (not included)
81
Ignition electrode
95
Mixing (diverting) valve
104(1) Fuse 3.15A
104 (1) Fuse 630mA
54
M
-
ALL
OUNT GAS
FIRED WATER BOILER
Boiler Manual
cod. 3541M870
114
Water pressure switch
136
Flow meter
138
Outside temperature sensor (optional on Combi)
186
Return temperature sensor
191
Exhaust temperature sensor
278
Double sensor (heating + safety)
279
Transformer 115-24 VAC
284
Relay SPST-Coil 24 VAC
370
LWCO (not included)
373
"OPENTHERM" communication (Not used)
Part number 550-100-305/0118