Weil-McLain Aqua Balance WMB-155 Manual page 106

Wall mount gas-fired condensing boilers-combi and heating only models
Table of Contents

Advertisement

W
TM
AquaBalance
34 Troubleshooting
Figure 134
Troubleshooting suggestions for
Some informations can be accessed with a communication package running on the PC.
Category
Description
Num. Address
Boiler
1
Boiler
2
Boiler
3
Boiler
4
Boiler
5
Boiler
6
Boiler
7
Boiler
8
Boiler
9
Boiler
10
Boiler
11
Boiler
12
Boiler
13
Boiler
14
Boiler
15
Boiler
16
Boiler
17
OpenTherm
18
OpenTherm
19
OpenTherm
20
D1....the boiler is / has finished the call for Domestic Water heating, and is in the transition to either standby mode or
central heating mode.
D2....the boiler has reached the required water set point, and the firing has stopped / with a call for Central Heating still
applied by the T-Stat to the boiler. Pumps will continue to operate and the boiler is monitoring the two internal water
sensors (return & discharge) waiting for a water "Delta-T" to return...at that time the boiler will re-fire if need be.
D3....the boiler has made 3 tries for ignition and has failed to ignite. A re-trial ignition cycle / delay is in effect for 3 more
tries to ignite.
Parameter Description
D1
After cycle of Domestic water mode, D1 will be displayed.
D2
When required boiler water set - point is reached D2 will be displayed.
D3
After an attempt for ignition, re-trial ignition delay is in effect (D3 is displayed).
&KHFN IRU SURSHU IXHO VXSSO\
5HPRYH DQG FKHFN LJQLWRU IRU SURSHU JDS ´ UHSODFH LI GLV¿JXUHG FKHFN FRPEXVWLRQ VHWWLQJ 1DWXUDO JDV RU /3
,QVXUH FRQGHQVDWH LV GUDLQLQJ SURSHUO\
,QVXUH YHQWLQJ VL]H DQG OHQJWK DUH FRUUHFW DQG XQREVWUXFWHG
106
M
-
ALL
OUNT GAS
FIRED WATER BOILER
(continued)
AquaBalance
Description
CL4 – A532
CH supply sensor1 temperature
CL4 – A567
CH supply sensor2 temperature
CL4 – A55B
CH return sensor temperature
CL4 -A53D
DHW sensor temperature
CL4 -A568
Exhaust sensor temperature
CL4 -1110
Water pressure sensor
CL4 -A554
Outside temperature sensor
CL4 -0FAB MSB
Control water set point
CL4 -FC02 MSB
CH Virtual set point
CL4 -FC02 LSB
DHW Virtual set point
CL4 – 11DC MSB
Fan speed -Setpoint
CL4 – 11DC LSB
Fan speed -Feedback
CL4 – 0364
Flame current
CL4 – FAFB MSB
PWM modulating pump
CL4 – FAFB LSB
Step of Triac modulating pump
CL4 – 0F0E
'+: ÀRZ VHQVRU
ML -F68B
DHW over-temp_burnerOFF-initially_Temperature
CL4 – FAF4 MSB
OT room setpoint
CL4 – FAF4 LSB
OT room setpoint
CL4 – FAC8 MSB
OT room temp
Boiler Manual
boilers — Fault displays and diagnostics
E2 prom parameters
(continued)
Unit
ƒ) 
ƒ) 
ƒ) 
ƒ) 
ƒ) 
3VL 
ƒ) 
°F
°F
°F
Hz
Hz
X$ 
%
Num
Hz
°F
°F Int
°F Dec
°F Int
Part number 550-100-305/0118