Location; Circulating Air Supply - Nordyne M2RC-080 Installation Instructions Manual

Direct vent (sealed combustion) forced air gas furnaces: m2rc series 90+ upflow and m2rl series 90+ downflow condensing furnace
Table of Contents

Advertisement

b. The Standard for Manufactured H ome
Installations (Manufactured
Home Sites,
Communities, and Set-Ups)ANSI A225.1
and/or CAN/CSA-2240
MH Series).
c.
American
National
Standard
(ANSI-
119.2/NFPA-501C)
for all recreational
vehicle installations.
d.
American
National
Standard
(ANSI-
Z223.1/NFPA-54)
and/or
CAN/CGA
B149 for all gas-fired furnace models.
e.
American National Standard (ANSI-C1/
NFPA-70) and/or CSA 22.1 Canadian
Electric Code Part 1 for all electrical field
wiring.
CE g6nerateur
d'air chaud dolt 6tre insta]l_
conform6ment
aux instructions du fabricant et
aux codes Iocaux. En I'absence de code local,
respecter la norme ANSI Z223.,1, institule Na-
tional Fuel Gas Code ou les codes d'installation
CAN/GCA-B 149.
The National Fuel Gas Code is available by
writing:
able and allow the appropriate clearance for
your installation.
This furnace
is certified
for use on wood
flooring. The furnace must be installed on a
solid surface and must be level front to back
and side to side. This furnace must not be
installed
directly
on carpeting,
tile, or any
combustible material other than wood flooring.
Downflow
models can only be installed on
combustible
flooring
when
installed
on a
Nordyne plenum base (part numbers 901987
through 901993 - see Table 5). Both the upflow
and downflow models must be installed with
the Nordyne A,'C coil box (part no. 914958).
The plenum attached to the A,'C coil box and
the ductwork within 3 feet of the furnace must
be installed such that surfaces are at least
1/4" from combustible
construction.
CIRCULATING
AIRSUPPLY
General
Plenums and air ducts must be installed in
AmericanNationaIStandardslnstitute,lnc.
'
accordance
with
the
Standard
for
the
1430 Broadway
Installati0n of Air Conditioning and Ventilating
New York, NY 10018
Systems (NFPA No. 90A) or the Standard for
the Installation of Warm Air Heating and Air
NFPA publications
are available by writing:
Conditioning
Systems (NFPA No. 90B).
National Fire Protection Association
Batterymarch
Park
Quincy, ME 02269
Location
The furnace must be installed on a level sur-
face, and as close to the center of the air
distribution
system as possible. See Figure 1
for overall dimensions
to determine
the re-
quired clearances in hallways, doorways, stairs,
etc. to allow the furnace to be moved to the
installation point. The furnace must be installed
so that all electrical components are protected
from water.
Minimum clearances to combustible materials
are listed in Table 4. Access for positioning and
servicing
must be considered when locating
the unit. 24 inches is the minimum required
clearance for servicing the unit. 30 inches is the
minimum required clearance for positioning the
unit. 36 inches is the recommended
clear-
ance from the front of the unit. Please note
that a panel or door can be located such that
the minimum clearance on the rating plate is
satisfied, but that panel or door must be remov-
/ WARNING:
Products
of combustion
must
not be
allowed to enter the return air openings
of the furnace or the circulating airsupply,
Failure
to
prevent
products
of
combustion
from being circulated
into
the living space
can create
potentially
hazardous
conditions
including
carbon
monoxide
poisoning
that could result in
personal
injury or death.
The floor or platform on which the fumace
is mounted must provide sound physical
support
of the furnace
with no gaps,
cracks, or sagging
between the furnace
and the floor or platform.
The circulating
air ductwork
must not be
connected
to any other heat producing
device such as a fireplace
insert, stove,
etc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

M2rc-100M2rl-060M2rl-100

Table of Contents