Operating, service and fault displays

14
Operating, service and fault displays
The control unit monitors all safety and control components.
The service and fault displays facilitate simple diagnosis using tables 35
and 36 below.
14.1

Service displays

If the
symbol appears on the display during normal operation, an
inspection is required.
To obtain details on service display 105:
▶ Press the info button.
Only one service display is ever shown.
Service
Service
display
code
Description
105
1
Burner runtime exceeded
105
2
Number of burner starts exceeded
105
3
Inspection interval reached
105
10
Replace heating controller batteries
105
22
Water pressure 3 heating circuit too
low (dropped below lower pressure
limit 3)
Table 35 Service displays
14.2

Fault displays

The presence of a fault is indicated on the display by symbol
To obtain details on the fault display:
▶ Press the info button.
Only one fault display is ever shown. The display sequence is made in
accordance with the priority specified in Tab. 36.

14.2.1 Fault Overview

Fault code
Description
10
Fault outside temperature sensor
20
Fault at boiler temperature sensor
28
Fault at flue gas temperature sensor
32
Fault at flow temperature sensor for heating
circuit 2
40
Fault at return temperature sensor
50
Fault DHW tank temperature sensor
52
Fault potable water temperature sensor
57
Fault at temperature sensor (DHW
circulation pump)
60
Fault at room temperature sensor 1
65
Fault at room temperature sensor 2
68
Fault at room temperature sensor 3
73
Fault at solar collector sensor
82
LPB address collision
83
BSB wire short circuit/no communication
84
BSB wire address collision
85
BSB wireless communication fault
91
Data loss in EEPROM
Table 36 Fault displays
42
Priority
6
6
6
6
9
.
Remedy
▶ Check sensor ( Tab. 37, 38, page 47); replace if required.
▶ Check lead for breaks or short circuits; replace if required.
▶ Check lead for breaks or short circuits; replace if required.
▶ Check sensor ( Tab. 37, page 47); replace if required.
▶ Check lead for breaks or short circuits; replace if required.
▶ Check call up (addressing) of the connected appliances.
▶ Check lead for breaks or short circuits; replace if required.
More than one controller is assigned to the same heating circuit.
▶ Assign one of the controllers to heating circuit 2 (refer to the
supplied accessories instructions).
▶ Check the connection of the wireless module to the appliance
electronics ( Fig. 15, page 16).
▶ Perform a communication test (see accessories supplement).
▶ Delete addressing for the heating controllers and reassign the
heating controllers (see accessories supplement).
▶ Replace the main PCB of the control unit.