Advertisement

Manual
Lynx Ion BMS
400A / 1000A

Advertisement

Table of Contents
loading

Summary of Contents for Victron energy Lynx Ion BMS 400A

  • Page 1 Manual Lynx Ion BMS 400A / 1000A...
  • Page 3: Safety Instructions

    1. SAFETY INSTRUCTIONS 1.1 In general Please read the documentation supplied with this product first, so that you are familiar with the safety signs en directions before using the product. This product is designed and tested in accordance with international standards. The equipment should be used for the designated application only.
  • Page 4: System Components

    2. DESCRIPTION Key features of the Lithium-Ion battery system.  Easy installation and usage  Integrated safety contactor used as second level protection  Active and passive balancing control capabilities (depending on connected battery module)  Separate CAN-Bus between USER and BMS CAN-Bus network ...
  • Page 5: Installation

    3. INSTALLATION This product may only be installed by a qualified electrical engineer. 3.1 Safety precautions Be careful when using metal tools in vicinity of batteries. Dropping a metal tool onto a battery might cause a short-circuit and possibly an explosion. Always use isolated tools when working with batteries.
  • Page 6 WARNING: Never connect loads and chargers directly to the batteries. This can damage the batteries. 3.4.2 Installing Fuses Fuses must be installed on both the battery side and load/charger side of the Lynx Ion BMS. The total value of the fuses in the Distributor on the load/charger side (right side) may not exceed maximum current of the safety contactor (an equal load ratio can be added depending on the application).
  • Page 7 Above solution can be used up to 5 batteries maximum. 3.4.4 Series connection of batteries The maximum battery in series is 2. This is because the standard maximum input voltage of the Lynx Ion BMS is 60 VDC.  Be sure that the battery state-of-charge is equal for each battery. If the batteries are new then they have an equal state-of-charge.
  • Page 8 Connect the network as following: To CAN-bus connection of the Lynx Ion BMS Do not forget the termination resistors at the ends of the CAN-Bus network. 3.4.6 Connecting to NMEA2000 network Use the AUX. CAN-Bus connection of the Lynx Ion BMS, for connection to a NMEA2000 network. For details see the Lynx Ion BMS communication guide.
  • Page 9 Use a momentary switch button for this. For example a Bulgin MPI002/TE/BL/12 which has a momentary switch and LED function integrated. Lynx-ion BMS...
  • Page 10 3.4.10 Auxiliary power output The auxiliary power output can be used to power a bilge pump or to power a display. This output will also be powered when the Lynx Ion BMS is in fail safe state. See appendix A, connection ‘A’ pin 1 and 6 for details. Example connection of Victron Color Control: Lynx-ion BMS 3.4.11 Programmable contact...
  • Page 11: First Power Up

    4 FIRST POWER UP Other than below procedure, no configuration is needed. The battery configuration is automatically recognized. 4.1 Power up procedure Make sure that all energy consumers are switched off before starting up the system, because the Lynx Ion BMS will pre-charge the system before closing the safety contactor.
  • Page 12 5 CONNECTING A VICTRON MULTI OR QUATTRO 5.1 Connection of a Multi or Quattro inverter/charger The Multi and Quattro needs to stop charging when the batteries are fully charged and stop discharging when the batteries are empty. To achieve this the allow-to-charge and allow-to-discharge signal contacts of the Lynx Ion BMS are used. See the switching boundaries document for details about the switching levels for your specific battery.
  • Page 13 5.2.2 Connecting 2 or more Multis or Quattros If 2 or more Multis or Quattros are connected to the Lynx Ion BMS then an additional relay needs to be installed to extend the Allow-to-charge and Allow-to-discharge contacts. Example: 2 Multis The Allow-to-charge and Allow-to-discharge will be extended by a relay with 2 separate contacts to control two Multis or Quattros.
  • Page 14 5.3 Configuration of a Multi or Quattro To configure the Multi for BMS support, VEConfigure3 is necessary. See the Support & downloads section at www.victronenergy.com for more information on installing VEConfigure3 and updating the Multi to firmware version xxxx200 or higher.
  • Page 15: Charger Settings

    Set action to: Disable charger when battery is full. (NOT force to float). Go to the charger tab and change the settings to the following: Set the absorption voltage and float voltage to the value’s specified in the table of chapter 6. 6 CHARGER SETTINGS In the table below are the voltage settings specified for different type of batteries.
  • Page 16 7 COMMISSIONING Below describes the procedure for commissioning the Lithium-Ion battery system. 7.1 Procedure Use the following procedure to verify the systems functionality: Check the firmware version of the Lynx Ion BMS:  The Lynx Ion BMS firmware version is updated to the latest release. Check that there are no loads or chargers connected directly to the batteries: ...
  • Page 17: Led Indications

     8 LED INDICATIONS Firmware version 1.XX and higher. Status LED state Description System is in standby mode. Press START button to start up the system Running Blinking Updating firmware of connected batteries Flashing/beeping 2 times Battery communication error (check BMS CAN-Bus cables) Flashing/beeping 3 times Under or overvoltage detected (check charger or load settings) Flashing/beeping 4 times...
  • Page 18: Technical Specifications

    Technical Specifications HE Battery 400A 1000 Maximum number of batteries in series 2 (= 48V) Maximum number of batteries in parallel Supply voltage range 18 ... 58VDC Standby mode 73 mW @ 26,2V and 138mW @ 52,4V Active mode 8,7 W Main safety contactor current continuous 400A 1000A...
  • Page 19: Appendix A: Connection Overview Of The Lynx Ion Bms

    APPENDIX A: Connection overview of the Lynx Ion BMS IO Connections Connector pins and specifications Pin I/O Voltage Current Purpose Conn. Aux. power output 13,5V Allow-to-Charge 13,5V Allow-to-Discharge 13,5V External start button External status output 13,5V 140mA Max. 0,8A @ 60VDC Allow-to-charge 60VDC Max.
  • Page 20: Appendix B: Inside The Lynx Ion Bms

    APPENDIX B: Inside the Lynx Ion BMS Part Description Mounting holes ‘-’ minus battery connections (M8 bolt connections) Plastic insulation part ´+´ positive battery connections (M8 bolt connections) Battery side fuses Loads/Chargers side fuses ‘+’ positive Loads/Chargers connections (M8 bolt connections) ‘-’...
  • Page 21: Appendix C: Dimensions

    APPENDIX C: Dimensions Dimensions in mm.
  • Page 22 Version : 03 Date : February 9 , 2018 Victron Energy B.V. De Paal 35 | 1351 JG Almere PO Box 50016 | 1305 AA Almere | The Netherlands General phone +31 (0)36 535 97 00 +31 (0)36 531 16 66 E-mail sales@victronenergy.com...

This manual is also suitable for:

Lynx ion bms 1000a

Table of Contents