Autotest in Far End Source Mode: Set the Reference
1
Turn on the tester and smart remote and let them sit for
5 minutes. Allow additional time if the modules have
been stored above or below ambient temperature. For
other sources, warm up according to the manufacturer's
recommendations.
2
Turn the rotary switch to SETUP, then select Fiber Loss.
Set the following on the Fiber Loss tabs (press
other tabs):
• Test Limit: Select the test limit required for the job.
J
Press
• Fiber Type: Select the fiber type to be tested.
• Remote End Setup: Set to Far End Source
Downloaded from
Elcodis.com
electronic components distributor
More to see other lists of limits.
• Bi-directional: Does not apply to Far End Source
mode.
• Number of Adapters and Number of Splices: Does
not apply to Far End Source mode.
• Connector Type: Select the connector type used in
the cabling to be tested. Select General if the exact
C
type is not listed.
to see
• Test Method: Refers to the number of adapters
represented in the loss results. Select 1 Jumper if you
use the reference and test connections shown in this
manual.
See Table 2 on page 15 for details on settings.
Certifying Fiber Cabling
-continued-