Setting Temperature Alarm Limits and Delay

(Shortcut: Press "A" and scroll down to 5.)
5)Temp Alarms
6)Temp Alarm Delay
Set High/Low Alarm Values
1)Hi Temp1 Alarm
2)Lo Alarm Alarm
Setting Negative Temperature Values
High temp above 0?
1)Yes 2) No
Setting Negative Temperature Values
Enter Hi Alarm:1
+120
Press "D" for Done
Set Delay Before Alarm
Shortcut: Press "A" and "6"
1) Temp 1 Delay
Enter minutes
0 for no delay
Press "D" for Done
01 minutes
This screen sets the trip values
of temperature. To automatically
cancel the alarm the value must be
greater (or less) than the trip value
by one degree.
Note that the temperature sensors
must be discovered (see page 8) in
order for high/low limits to be set.
This function permits 0 - 99 minutes
of delay before sending a text alarm.
The primary purpose is to ignore
defrost cycles where the temperature
can routinely and briefly jump to
20degF higher than normal.